欢迎访问ic37.com |
会员登录 免费注册
发布采购

AME40-12SMAZ 参数 Datasheet PDF下载

AME40-12SMAZ图片预览
型号: AME40-12SMAZ
PDF下载: 下载PDF文件 查看货源
内容描述: 40瓦| AC- DC转换器 [40 Watt | AC-DC Converter]
分类和应用: 转换器
文件页数/大小: 3 页 / 764 K
品牌: AIMTEC [ AIMTEC ]
 浏览型号AME40-12SMAZ的Datasheet PDF文件第2页浏览型号AME40-12SMAZ的Datasheet PDF文件第3页  
Series AME40-MAZ
40 Watt | AC-DC Converter
FEATURES:
4000VAC I/O isolation
Medical Switching power modules for PCB mounting
Operating temperature: -40 to +85°C
Universal Input: 90-260VAC, 47-440Hz, or 120-370VDC
Energy star compliant
RoHS compliant
Low Ripple and Noise
CE, cULus approvals
Models
Single output
Model
AME40-3.3SMAZ
AME40-5SMAZ
AME40-12SMAZ
AME40-15SMAZ
AME40-24SMAZ
CB
Input Voltage
(VAC/Hz)
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
90-264/47-440
Input Voltage
(VDC)
120-370
120-370
120-370
120-370
120-370
Output Voltage
(V)
3.3
5
12
15
24
Output Current
max
(A)
8
8
3.33
2.66
1.66
Efficiency
(%)
78
82
84
83
82
Models
Dual output
Model
AME40-5DMAZ
AME40-12DMAZ
AME40-15DMAZ
AME40-24DMAZ
Input Voltage
(VAC/Hz)
90-264/47-440
90-264/47-440
90-264/47-440
90-260/47-440
Input Voltage
(VDC)
120-370
120-370
120-370
120-370
Output Voltage
(V)
±5
±12
±15
±24
Output Current
max
(A)
±4
±1.66
±1.33
±0.835
Efficiency
(%)
80
85
82
77
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Input Specifications
Parameters
Current
Inrush current <2ms
Leakage current
External fuse
Input dissipation
No load; 264VAC
Start-up time
<0.8
117
Conditions
115 VAC
230 VAC
115 VAC
230 VAC
Recommended slow blow type
No load; 115VAC
Typical
Maximum
1000
530
25
50
150
Units
mA
mA
A
A
µA
A
W
ms
3.15
<0.5
Output Specifications
Parameters
Voltage accuracy
Line regulation
Load regulation
Cross regulation
Maximum Capacitive load
Transient response deviation
Ripple & Noise*
Hold-up time (min)
Minimum Load Current
www.aimtec.com
F 052e R8.D
Conditions
(LL-HL)
0-100% load single
0-100% load dual
25% load - 1
st
out, 100% load – 2
nd
out
Depending of the model
25% load Step
20MHz bandwidth
115VAC
Typical
±2
±0.5
±1
±2
±5
470-23 000
±2
50
29
0
Maximum
Units
%
%
%
%
µF
% of Vout
mV p-p
ms
% of Max
Tel: +1 514 620 2722
1 of 3
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only