D-Series Circuit Breaker - General Specifications | 3
Electrical Tables
Table A:
Lists UL Recognized, CSA Accepted and VDE Certified configurations and performance capabilities as a
Component Supplementary Protector.
Table A Notes:
1
DC and 1Phase 277 V ratings are 1 or 2 poles breaking. Three phase ratings are 3 poles breaking.
2
Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4 times full
load amps not to exceed 150 A for 250V rating and 125 A for 277 and 480 V ratings.
3
UL recognition and CSA Acceptance at 480 volts refers to 3 and 4 pole versions, used only in a 3 phase WYE connected
circuit or 2 pole versions connected with 2 poles breaking 1 phase and backed up with series fusing per note 2
Agency Certifications
UL Recognized
UL Standard 1077
Component Recognition Program
as Protectors, Supplementary
(Guide QVNU2, File E75596)
Switches, Industrial Control
(Guide NRNT2, File E148683)
CSA Accepted
Component Supplementary
Protector under Class 3215 30,
File 047848 0 000
CSA Standard C22.2 No. 235
EN60934, VDE 0642 under File
No. 10537
UL Listed
UL Standard 508
VDE Certified