Programming (Continued)
When the sensor head is inserted into the base, the
address is automatically relayed to the sensor. Changing
the sensor does not require additional programming since
the address remains on the XPert card located in the base.
All other sensor-specific programming is accomplished at
the FACP.
Specifications (Continued)
Relay Versions Only:
Relay Contacts:
Two dry Form-C contacts
Relay Contact Ratings:
10 A @ 24 VDC resistive
maximum
Operating Voltage:
24 VDC
Current:
Standby current:
0.010 A @ 24 VDC
Alarm current:
0.055 A @ 24 VDC
Engineer’s Specifications
The contractor shall furnish and install, where indicated on
the plans, analog addressable air duct smoke detectors.
The sensors shall be listed by Underwriter’s Laboratories
per UL 268A and UL-Listed as compatible with the Fire
Alarm Control Panel (FACP). The sensors shall operate at
air velocities from 300 to 4,000 feet
(91.44 to 1219.20 m)
per
minute. The smoke sensor shall contain an integral LED
that shall latch in when the unit goes into alarm, mounted at
a 30° slant to provide a wide viewing angle.
A manual reset/test switch shall be located on the front of
the device. The housing shall contain a sensor base which
will accept photoelectric or ionization heads. All wiring must
comply with local codes and regulations. The duct sensor
housing shall have a metal chassis with a clear plastic
cover and complete mechanical installation may be per-
formed without removal of the cover. The duct smoke
detector shall be the Gamewell-FCI model, XP95-ID(R) or
XP95-PD(R) analog addressable duct smoke detector.
Ordering Information
Description
Two-wire air duct, ionization smoke detector
24 VDC (RW-AAN)
XP95-PD
Two-wire air duct, photoelectric smoke
detector 24 VDC (RW-AAP)
30203-01
Remote LED alarm indicator (two VDCs);
used with XP95-PD and XP95-ID
XP95-IDR
Four-wire air duct, ionization smoke detector
24 VDC with relay (RW-ARN)
XP95-PDR
Four-wire air duct, photoelectric smoke
detector 24 VDC with relay (RW-ARP)
30203
Remote LED alarm indicator (24 VDCs);
used with relay versions
30007-02
Remote test station with alarm LED;
used with relay versions
70896-02
Sampling tube, 2.5 feet
(0.762 m)
70896-05
Sampling tube, 5 feet
(1.524 m)
70896-10
Sampling tube, 10 feet
(3.048 m)
XP95-I
Ionization sensor head (replacement)
XP95-P
Photoelectric sensor head (replacement)
72247
Duct detector enclosure (WP-1)
(See Data Sheet CS-2308).
Model
XP95-ID
Specifications
Ambient Temperature:
32° F to 120°F (0°C to 49°C)
Humidity:
10% to 85% R.H
Material:
18 gauge steel backbox,
clear plastic cover
Dimensions:
10.0" H x 8.25" W x 2.25" D
(25.4 H x 21.0 W x 5.7 D cm)
Maximum Net Weight:
4.0 lbs.
(1.814 kg)
Mounting:
Template and necessary
hardware supplied
Radioactive Element:
For Ionization versions only:
Americium 241 (0.9 microcuries)
Sensitivity:
Factory set (ion); or adjustable
via the IF600 control panel
(photoelectric)
Air Velocity:
300 to 4,000 feet per minute.
Pressure Differential:
0.01 to 1.2 inches
(1.524 to 20.320
meters per second)
of water
Standby Current:
Photoelectric: 340 µA
Ionization:
280 µA
Alarm LED Current:
Photoelectric: 4 mA
Ionization:
2 mA
Remote Alarm Output
20 mA maximum; diode gated
Range:
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2049 Rev. a1 page 2 of 2
www.gamewell-fci.com
GAMEWELL-FCI