Specifications:
Ordering Information:
Standby Current:
Photoelectric, combination
photo/heat, or ionization:
30 to 45 µA @ 24 volts.
71033
Conventional photoelectric smoke
detector head.
71034
Conventional ionization smoke detec-
tor head.
Alarm Voltage:
6 to 28 volts.
Normal Alarm Output: 52 mA @ 24 volts.
Remote Alarm Output: 20 mA maximum, diode gated.
Temperature Range:
71443
Conventional combination photo/heat
smoke detector head.
71035
Conventional thermal heat detector
head (135°F [57.2°C]).
Photo/Comb/Ion/
71035-160
71035-210
71036
Conventional thermal heat detector
head (160°F [71.1°C]).
Thermal
32°F to 140°F (0°C to 60°C)
-5° F to 195° F
(-20.5°C to 90.5°C)
0% to 95% relative humidity
(no condensation)
Thermal:
Conventional thermal heat detector
head (210°F [98.8°C]).
Humidity:
Conventional 4.0" (10.16 cm) detector
base.
Recommended
Spacing:
71086
Conventional 6.0" (15.24 cm) detector
base.
Per NFPA codes.
Alarm Current:
6.0 (15.24 cm) detector base with
relay:
72 mA @ 24 volts.
71086-RED
Conventional 6.0" (15.24 cm) detector
base with flashing power-indicating
red LED.
71086-GREEN Conventional 6.0" (125.24 cm) detector
base with flashing power-indicating
green LED.
71086-SNDR
Conventional 6.0" (15.24 cm) detector
base with sounder.
71393
Conventional 4.0" (10.16 cm)
detector base with relay and flashing
power-indicating green LED.
71086-LOW
Conventional 6.0" (15.24 cm) low-pro-
file detector base.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
CS-2484 Rev. B page 3 of 3