TABLE 2 : DBA RATINGS FOR 12 VDC & 2 4 VDC SERIES  
AS/AH 1 2 & 24 VDC AUDIBLE  
TABLE 1: RATINGS PER UL 1971  
REGULATED  
INPUT  
VOLTAGE  
VDC  
STROBE  
CANDELA  
(cd)  
VOLTAGE  
RANGE  
VDC/FWR  
MODEL  
REV ERBERA NT  
DBA PER UL  
464 @ 10 FT .  
A NEC HOIC  
DBA  
@ 10 FT .  
DESC RIPT ION  
V OL UM E  
AS-24MCW  
AS-241575W  
AS-121575W  
AS-24MCC  
24  
24  
12  
24  
16.0 - 33.0  
16.0 - 33.0  
8.0 - 17.5  
16.0 - 33.0  
15/30/75/110  
15 (75 on axis)  
15 (75 on axis)  
15/30/75/95  
High  
Medium  
Low  
91  
88  
83  
87  
84  
79  
99  
95  
90  
99  
95  
90  
Continuous  
Horn  
High  
ASWP-2475W  
24  
16.0 - 33.0  
75 @ -31°F  
Code 3 Horn  
Medium  
Low  
TABLE 3: AVERAGE RSM CURRENT*  
AUDIBLE  
WALLMOUNT AUDIBLESTROBE MODELS  
CELING MOUNT STROBEMODELS  
AS-24MCC AS-24MCCH  
115cd 177c d  
24 VDC MODELS  
AH-24  
AS-241575W  
15/ 75c d  
AS-24MCW  
3 0 c d  
AS-24MCWH  
15cd  
75cd  
0.219  
0.157  
0.138  
0.203  
0.133  
0.206  
0.201  
0.126  
0.094  
110 c d  
0.303  
0.197  
0.166  
0.282  
0.179  
0.134  
0.279  
0.169  
0.121  
13 5c d  
0.355  
0.250  
0.210  
0.340  
0.230  
0.180  
0.335  
0.220  
0.170  
18 5c d  
0.480  
0.320  
0.250  
0.465  
0.305  
0.230  
0.460  
0.295  
0.215  
15c d  
3 0 c d  
0.145  
0.120  
0.113  
75c d  
9 5cd  
16 vdc  
HIGH  
0.035  
0.050  
0.069  
0.020  
0.026  
0.035  
0.014  
0.014  
0.021  
0.0130  
0.0107  
0.0105  
0.114  
0.099  
0.093  
0.098  
0.078  
0.065  
0.065  
0.070  
0.052  
0.046  
0.135  
0.114  
0.105  
0.970  
0.101  
0.084  
0.069  
0.068  
0.076  
0.056  
0.049  
0.238 0.330  
0.355 0.480  
0.250 0.320  
0.210 0.250  
(99)  
dBA  
24 vdc  
33 vdc  
16 vdc  
24 vdc  
33 vdc  
16 vdc  
24 vdc  
33 vdc  
0.169  
0.146  
0.213  
0.177  
0.108  
0.116  
0.126  
0.094  
0.083  
0.121  
0.084  
0.068  
0.222 0.309 0.340 0.465  
MEDIU  
M
(95)  
dBA  
0.085  
0.075  
0.108  
0.088  
0.078  
0.111  
0.145  
0.114  
0.195  
0.145  
0.230 0.305  
0.180 0.230  
0.220 0.306 0.335 0.460  
LOW  
(90)  
dBA  
0.075  
0.060  
0.077  
0.063  
0.138  
0.102  
0.185  
0.132  
0.220 0.295  
0.170 0.215  
WALL  
MOUNT  
AUDIBLE  
STROBE  
WALL  
MOUNT  
AUDIBLE  
STROBE  
WALL  
MOUNT  
AUDIBLE  
STROBE  
AUDIBLE  
A H- 12  
AUDIBLE  
AUDIBLE  
A H- 12  
12 VDC MODELS  
12 VDC MODELS  
8 vdc  
12 VDC MODELS  
A S- 12 1575W  
A H- 12 A S- 12 1575W  
A S- 12 1575W  
8 vdc  
HIGH  
0.093  
0.108  
0.128  
0.320  
0.260  
0.220  
0.037  
0.049  
0.069  
0.275  
0.195  
0.160  
8 vdc  
LOW  
0.030  
0.035  
0.042  
0.265  
0.175  
0.133  
MEDIUM  
(99)  
dBA  
(90)  
dBA  
12 vdc  
12 vdc  
12 vdc  
(95) dBA  
17.5vdc  
17.5vdc  
17.5vdc  
*Average RSM Current is per UL average method and Average Mean Current is per UL average mean method. AH and AS-12 models use  
average mean current. For rated in Rush and Peak current across the UL listed voltage range for both filtered DC and unfiltered VRMS  
(FWR), see installation instructions.  
NOTES:  
SYNC MODELS/POWER SUPPLY  
SM Sync Module is rated for 3.0  
amperes @ 24 VDC.  
AVERAGE  
INPUT  
M ODEL  
M EAN  
MOUNTING  
DSM Sync Module is rated for 3.0  
amperes per circuit. The maximum  
number of interconnected DSM  
modules is twenty (20).  
VOLTAGE  
(VDC)  
NUMBER  
CURRENT  
@ 24 VDC  
OPTIONS*  
SM-12/24-R  
24  
24  
.028  
.035  
W
W
DSM-12/24-R  
The Gamewell Company  
12 Clintonville Road  
*Refer to mounting options data  
sheet.  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
Specifications and wiring information are provided for information only and are believed  
to be accurate. Gamewell assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring  
instructions shipped with the product shall always be used for actual installation. For  
more information, contact Gamewell.  
www.gamewell.com  
A Honeywell Company  
© 2004 Gamewell  
Page 4 of 4  
AS Series & AH Series CS-2231 06/01/04