欢迎访问ic37.com |
会员登录 免费注册
发布采购

ASD-PTL2F 参数 Datasheet PDF下载

ASD-PTL2F图片预览
型号: ASD-PTL2F
PDF下载: 下载PDF文件 查看货源
内容描述: 模拟,可寻址光电烟雾传感器 [Analog, addressable photoelectronic smoke sensor]
分类和应用: 光电传感器
文件页数/大小: 2 页 / 197 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号ASD-PTL2F的Datasheet PDF文件第2页  
Velociti Series
ASD-PL2F and
ASD-PTL2F
Description
The Gamewell-FCI Velociti
®
Series, analog address-
able plug-in smoke sensors with integral communica-
tion provide features that surpass conventional
sensors. Sensitivity can be programmed in the con-
trol panel software, and is continuously monitored
and reported to the panel. Point ID capability allows
each sensor’s address to be set, providing exact
locations for selective maintenance when the cham-
ber contamination reaches an unacceptable level.
The ASD-PL2F photoelectric sensor’s unique optical
sensing chamber is engineered to sense smoke pro-
duced by a wide range of combustion sources. Dual
electronic thermistors add 135°F (57°C) fixed-tem-
perature thermal sensing on the ASD-PTL2F model.
The Velociti
®
Series use a communication protocol
that substantially increases the speed of communica-
tion between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the panel’s
microprocessor stops the group poll and concen-
trates on the single device. The net effect is a
response speed up to five times greater than earlier
designs.
®
Analog, Addressable Photoelectronic
Smoke Sensor
ASD-PL2F
ASD-PTL2F
Features
• Sleek, low-profile design
• Visual rotary, decimal switch addressing (01-159)
• Built-in functional test switch activated by an external
magnet
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm*
• Optional relay, isolator, or sounder bases
• Low standby current
• Analog addressable communication
• Stable communication technique with noise immunity
• Optional remote, single-gang LED Indicator (RA400Z)
• Suitable for installation in ducts
• Compatible with Gamewell-FCI analog addressable
panels
Note: *Only the red LED is operative in panels that do not operate
in Velociti
®
mode.
Ordering Information
Model
Description
ASD-PL2F
Analog, addressable photoelectronic
smoke sensor
ASD-PTL2F
Analog, addressable photoelectronic smoke
sensor with thermal sensing
An ISO 9001-2000 Company
SIGNALING
Velociti
®
is a registered trademark of Honeywell International Inc.
UL is a registered trademark of Underwriters Laboratories Inc.
®
S1913
FM
APPR OVED
Approved
3023594 219-02-E Vol.VI 07272-0694:263
MEA
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0617 Rev. E1 page 1 of 2
©2008 by Honeywell International Inc. All rights reserved.
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
GAMEWELL-FCI