欢迎访问ic37.com |
会员登录 免费注册
发布采购

ATU 参数 Datasheet PDF下载

ATU图片预览
型号: ATU
PDF下载: 下载PDF文件 查看货源
内容描述: 释放装置单位/中止定时器单元 [Releasing Device Unit/Abort Timer Unit]
分类和应用: 装置
文件页数/大小: 1 页 / 83 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
   
7200 SERIES
RDU/ATU
RELEASING DEVICE UNIT/
ABORT TIMER UNIT
RDU
ATU
DESCRIPTION
The Releasing Device Unit (RDU) provides the 7200 Series fire alarm control panel with the ability to control the operation
of up to ten (10) fire suppression systems and also provides communication with all sensors and control modules used for op-
eration of these systems. It contains a 20-character display to indicate the state of any of its suppression systems.
The RDU features a signaling line circuit that can accommodate 99 analog sensors and 98 monitor and/or output modules
(AMM-2/-4, AOM-2). It also provides an RS-485 circuit for connection of up to 31 remotely located Abort/Timer Units
(ATU).
Sensors can be cross-zoned or configured in a counting zone for automatic activation of a suppression system. Monitor mod-
ules may be used in conjunction with manual release stations, abort switches and “squirt” switches for reactivation of a dis-
charge control.
Control modules can be configured for any of the following:
·
Notification Appliance Circuit
·
Prealarm interlock
·
Releasing
·
Prerelease interlock
·
Time-Limit-Cutoff interlock
·
Release interlock
Compatible solenoids for use with the control modules used for releasing are:
·
Skinner Models LV2LBX25, 73218BN4UNLVNOC111C2, 73212BN4TNLVNOC322C2,
71395SN2ENJ1NOH111C2, 24 VDC.
·
Asco Models T8210A107, 8210G207, 24 VDC
A “DISCONNECT” switch is provided for the circuit and allows the system to be serviced and/or tested without activating
any releasing devices. LEDs mounted on the RDU include a red “ALARM” LED and yellow “TROUBLE” LED for its signal-
ing line circuit.
A pluggable terminal block is provided on the RDU for the connection of all circuits. This terminal block will accommodate
wire sizes up to 12 AWG.
The Releasing Device Unit (RDU) is a full-size unit and mounts in any available module position.
The Abort/Timer Unit (ATU) is an addressable abort switch containing a display for an individual suppression system. Upon
suppression system activation by either manual or automatic means, the display indicates the time remaining until suppression
discharge. The ATU may be remotely located and mounts on a conventional 3-gang electrical box.
TECHNICAL AND ORDERING INFORMATION
Part
Number
1100-1224
1100-1223
Model
RDU
ATU
Supervisory
Current
0.065 amp.
0.014 amp.
Alarm
Current
0.085 amp
0.030 amp.
Description
Releasing Device Unit
Abort Timer Unit
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 1997 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0463/Ver. 1.1