欢迎访问ic37.com |
会员登录 免费注册
发布采购

CPD-7051 参数 Datasheet PDF下载

CPD-7051图片预览
型号: CPD-7051
PDF下载: 下载PDF文件 查看货源
内容描述: 离子感烟火灾探测器 [IONIZATION SMOKE DETECTOR]
分类和应用:
文件页数/大小: 2 页 / 57 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号CPD-7051的Datasheet PDF文件第2页  
CPD-7051
IONIZATION SMOKE DETECTOR
DESCRIPTION
The CPD-7051 dual chamber ionization smoke detector
senses both visible and invisible products of combustion and
is designed for 2-wire and 4-wire system operation. The 360
o
smoke entry characteristic permits maximum smoke
response from any direction.
To assure that the detector is functioning, an LED pulses
approximately every 4 seconds to allow for visual
supervision of the detector. Under alarm condition, the LED
lights constantly at full brilliance. An optional base is
available to provide a remote LED function.
A unique gated output circuit design provides improved
stability and transient suppression. Special signal processing
techniques verify the presence of smoke before the detector
will alarm.
Installation of the detector is easy and quick because of
non-polarized connections. The detector head is fixed to the
base by a twist-lock action.
Both functional and sensitivity testing of the device may be
accomplished by means of a test magnet. This simulates the
effect of smoke (approximately 1.3 % per foot obscuration)
entering the chamber.
In addition, the actual sensitivity of the detector may be
measured in direct readout of percent per foot obscuration
with a sensitivity tester and standard voltmeter without the
necessity of removing the detector.
An insect screen protecting the chamber is used to avoid
potential nuisance alarms.
CPD-7051 ionization detectors may be inter-changed with
PSD-7155 or PSD-7156 photoelectric detectors. Optional
bases are available for remote test, indication, 4-wire
operation and/or control functions. See Table 1. In addition,
an MA-001 adapter is available to enable the CPD-7051 to
mount in existing CPD series bases.
APPROVALS
UL (Std 268)
Factory Mutual
C.S.F.M.
New York City MEA
S 1913
0W3A2.AY
7271-1076:115
346-92-E
FEATURES
High Air Flow Dual Chamber
Flashing LED for Visual Supervision
Remote and Local Functional Test
Capability
In-place Sensitivity Measurement in
Percent per Foot Obscuration
Two and Four-wire Low Current
Design
Non-polarized
Surface Mount Technology
High Altitude Operation
Interchangeable Bases
TECHNICAL SPECIFICATIONS
Nominal sensitivity
Standby voltage
Standby current
Operating temperature
Humidity
Air velocity
Altitude
Area of coverage
Radioactive source
1.3 %/ft.
10.2 to 36.8 VDC (24 VDC nominal)
45 uA. (typical) 100 uA. peak @ 24 VDC
32
o
to 100
o
F (0
o
to 49
o
C)
0-93% relative humidity (non-condensing)
1,000 feet per minute, gusts to 2,000 fpm per UL268
Up to 7,500 feet
30 ft. centers (900 sq. ft. max.) (smooth ceilings)
0.7 microcuries Americium 241 (sealed)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com
9020-0303 Rev. H
1 of 2