欢迎访问ic37.com |
会员登录 免费注册
发布采购

CTX-95 参数 Datasheet PDF下载

CTX-95图片预览
型号: CTX-95
PDF下载: 下载PDF文件 查看货源
内容描述: 市领带扩展提供了一个反向极性城市connextion可寻址循环 [City tie expander provides one reverse polarity city connextion for addressable loop]
分类和应用:
文件页数/大小: 2 页 / 83 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号CTX-95的Datasheet PDF文件第2页  
CTX-95
Description
The Gamewell-FCI City Tie Expander (CTX-95) is a single-
circuit, reverse-polarity transmitter that provides the inter-
face between the Fire Alarm Control Panel (FACP) and a
municipal system or central station. The CTX-95 connects
to the panel via a three-wire SLC circuit. The most common
usage is transmitting supervisory signals and their faults on
a separate city tie from the main system, and to transmit
alarms to a central station to indicate building alarm or
arrival entrance to building.
The CTX-95 is either surface or flush mounted and has an
integral LED that lights at device activation.
City Tie Expander
g2282ph1.jpg
Operation
The CTX-95 is a programmable reverse polarity city tie cir-
cuit. The module contains the XP-95 protocol to communi-
cate with the Gamewell-FCI 600 Series of analog
addressable control panels. The module provides the
power and supervision for the reverse polarity city tie. Pro-
gramming CTX-95 selected circuits insures that only their
alarms and troubles are transmitted to the central station.
CTX-95
CTX-95
Features
Compatible with all Gamewell-FCI 600 Series analog
addressable FACPs.
Connects to addressable SLC.
Provides one reverse polarity circuit.
Over-voltage protector built-in.
LED annunciates activation.
Fully supervised.
Surface or flush mounting.
Field programmable.
Style 4, 6, or 7 wiring.
Programming
The CTX-95 is programmed by setting a single DIP switch
easily accessible on the device’s printed circuit board. The
DIP switch is used to set the address of the CTX-95. All
other programming is accomplished at the Fire Alarm Con-
trol Panel, either through a laptop computer or through the
Control Panel Operator’s Display.
Screw terminals for field-wiring connections.
Mounting
The CTX-95 mounts in a standard 4.688"
(11.908 cm)
electri-
cal backbox. The CTX-95 should be mounted in an easily
accessible location so that the LED may be seen for quick
indication of proper connection and activation.
An ISO 9000-2000 Company
SIGNALING
Microsoft
®
Windows
®
is a registered trademark of Microsoft
®
Corporation.
S521
7300-1288:147
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2042 Rev. A page 1 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2042ph2.wmf