DACT-E3
Description
The Digital Alarm Communicator Transmitter (DACT-E3) is
an optional component of the E3 Series
®
Expandable
Emergency Evacuation System. The DACT-E3 sends digi-
tal signals over the telephone network to a central station.
This module can be located in the main cabinet or remotely
located via a local RS-485 serial interface.
The DACT-E3 is compatible with digital alarm communica-
tor receivers (DACRs) that receive the following signaling
formats:
• SIA DC8
• 3+1 2300 Hz
• SIA DCS20
• 4+2 1400 Hz
• Ademco Contact ID
• 4+2 2300 Hz
• 3+1 1400 Hz
In addition to the DACT-E3 being compatible with digital
signaling formats, the DACT-E3 features numerous for-
mats for communication to a central station. As a digital
communicator, the DACT-E3 complies with FCC Part 8,
Telecommunication Standards for DC and AC Ringer
Equivalence.
Digital Alarm
Communicator Transmitter
DACT-E3
Features
• Listed under UL Standard 864, 9th Edition
• Communicates with the E3, ILI-MB-E3 sub-assembly
via RS-485
• Communicates in a variety of formats
• Transmits and verifies data to the central station
• Offers pre-programmed dialing to the central station
phone number
• Performs on and off-hook status to the phone lines
• Traces proper central station “ACK” and “Kiss-off” tone
• Activates hang-up and release phone lines
Installation Instructions
The DACT-E3 is adaptable for installation in standard E3
Series
®
System cabinets. Typically, the DACT-E3 module
mounts on standoffs on top of the left side of the ILI-MB-E3
module. Either unit can be easily connected to the backbox
or sub-assembly plate depending on the cabinet module.
Note: For instructions on installing the DACT-E3, refer to
the E3
Expandable Emergency Evacuation Instal-
lation/Operating Manual, Part Number: 9020-0574 or the
DACT-E3 Installation Instructions Part Number:9000-0580.
Series
®
Specifications
24 VDC
(from PM-9 power supply)
Operating Current:
0.018 amp.
Alarm Current:
0.018 amp.
Operating Temperature:
32° to 120° F (0 to 49° C)
Relative Humidity:
0 to 93%, non-condensing at
90° F (32° C)
E3 Series
®
and NetSOLO
®
are registered trademarks of Honeywell International Inc.
Ordering Information
Model
DACT-E3
Operating Voltage:
Description
Digital alarm communicator transmitter
An ISO 9000-2000 Company
SIGNALING
FM
APPROVED
MEA
Approved
City of
Chicago
Approved
Class 1
Class 2
High Rise
S1869
3025415 231-06-E
7165-0694:268
7165-0694:269
City of
Denver
Approved
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell-fci.com
9020-0610 Rev. e1 page 1 of 1
©2007 by Honeywell International Inc. All rights reserved.
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118