FC-73
www.firecontrolinstruments.com
IntegralDACTConnections
ZONE
NAC
DISCONNECT
SWITCH
DISCONNECT
SWITCH
RIN G
TIP
RI N G
TIP
RIN G
TIP
RIN G TIP
55 P2 54
61 T1 60
59 P1 58
57 T2 56
(TYPICAL)
(TYPICAL)
3ProgrammableFormCRelayOutputs
2.5amps.@24VDC/24VAC(inductive)
5amps.@24VDC(resistive)
Nonpower-limited
ALARM
SUPERVISORY TRO UBLE
SILENC ED
POWER
TEST
10StyleBor5StyleD
InitiatingDeviceCircuits
Max.Voltage-25.5VDC
Max.CircuitResistance- 50Ohms
ACK
SILENC E
RESET
DRILL
TotalAlarmCurrentforallCircuits-1.0amp.
SupervisoryCurrentperZone-0.003amp.
AlarmCurrentperZone-0.095amp.
Power-Limited&Supervisedwith3.9KW EOL
(notrequiredforStyleDcircuits)
MunicipalCircuitOutput
ReversePolarityOutput
ZONE 1
ZONE 11
NAC 1
ZONE 12
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
ZONE 10
4StyleYor2StyleZ
NotificationApplianceCircuits
Power-limited&Supervised
with3.9KW EOLresistor(StyleYonly)
3.0amps.max.outofanyonecircuit
NAC 2
NAC 3
NAC 4
ZONE 14
ZONE 16
ZONE 17
ZONE 18
ZONE 19
ZONE 20
SBUS&AuxliaryPower
1.0amp. max. @24VDC
MASTER
BOX
Connectionto120VAC
3amps. @60Hz
®
FIRE CONTROL
INSTRUMENTS
FIRE ALARM CONTROL
MODEL FC-73
ZONEINDICATING LEDs
RED/YELLOW= ALARM/SUPERVISO RY OFF-NORMAL
YELLOW= ZONE TRO UBLE
(TYPICAL)
NAC INDICATING LEDs
GREEN= CIRCUITACTIVE
YELLOW= CIRCUIT TRO UBLE
TYPIC AL
MountingLocationforZDM-FC73orFC-5280
(ZDM-FC73canmountremotelyinFC-2190AccessoryCabinet)
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice.
© 2001 All Rights Reserved
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com
9020-0523 Rev. B / Page 3 of 4