内容描述: Gamewell - FCI电源6 [Gamewell-FCI Power Supply 6]
分类和应用:
文件页数/大小: 2 页 / 53 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号GFPS-6的Datasheet PDF文件第2页  
GFPS-6
Description
The Gamwell-FCI Power Supply 6 (GFPS-6) panel provides
either two (2) Class A, Style Z, four (4) Class B, Style Y, or
one (1) Class A and two (2) Class B notification appliance
circuits, with a total capacity of 6 amperes. These circuits
may be activated in groups by connection to one (1) or two
(2) existing Class A or B notification appliance circuits with
operating voltages ranging from 9 to 32 VDC. Either non-
coded or coded operation is possible. In addition, the
GFPS-6 can provide a temporal pattern Class B output from
a non-coded input.
A unique feature allows for programmable synchronized
outputs for strobes by four (4) different major manufactur-
ers, System Sensor, Faraday, Gentex or Cooper-Wheelock.
The GFPS-6 contains its own battery charger capable of
maintaining batteries of up to 33 AH. The cabinet provides
space for a set of 7 A/H batteries. It is supervised for
ground fault, over-current, open circuits and low battery
conditions.
Ground fault, battery and circuit trouble conditions in the
panel automatically open the notification appliance circuit
used for activation, transmitting a trouble signal to the main
fire alarm control panel. The ground fault detection circuit
may be disabled.
The unit contains a set of dry, Form “C” trouble actuated
auxiliary contacts, rated 2.5 amp. @ 24 VDC (resistive).
Transfer of these contacts for AC power failure can be
delayed for a period of six (6) hours. This delay feature may
be disabled.
A power-limited, non-resettable auxiliary power output is
also available. The panel can be programmed via DIP
switch to disconnect the auxiliary power output from the
batteries 30 seconds after AC power failure, in order to
avoid running down the batteries from high current devices
such as door holders, etc.
Gamewell-FCI Power Supply 6
GFPS-6
Features
UL Listed as a fire alarm accessory for use with any
Gamewell-FCI or other UL Listed fire alarm controls.
Two (2) Class A (Style Z), or four (4) Class B (Style Y)
notification appliance circuits or one (1) Class A and
two (2) Class B circuits.
Programmable ANSI S3.41 temporal pattern output
(Class B).
High current 6 amp. total output.
Integral strobe synchronization feature for strobes by
three (3) manufacturers.
Integral ground fault detection.
Form “C” trouble contacts with delayed AC failure
indication.
An ISO 9000-2000 Company
SIGNALING
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-60235 Rev. A page 1 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2049ph1.wmf