 浏览型号HPF24S6的Datasheet PDF文件第2页  
HPF24S6 and
HPF24S8
Description
The HPF24S6 and HPF24S8 are compact, cost-effective, 6
amp. or 8 amp. remote power supplies with integral battery
chargers. These adaptable power supplies may be con-
nected to any 12 or 24 volt Fire Alarm Control Panel
(FACP) or the power supplies may stand alone. Primary
applications include the following:
• Notification Appliance Circuits (NAC) expansion to sup-
port ADA requirements and NAC synchronization
• Auxiliary power to support 24 volt system accessories
HFP24S6/8
dh1061.jpg
Power Supplies with Battery Chargers
These power supplies provide regulated and filtered 24
VDC power to four (4), notification appliance circuits, con-
figured as either four Class B (Style Y) or Class A (Style A,
with ZNAC-4 Option Module). Alternately, the four outputs
may be configured as follows:
• all non-resettable
• all resettable
• two non-resettable
• two resettable
The power supplies also contain a battery charger with a
charging capacity of up to 18 Amp Hour batteries.
The HPF24S6 and HPF24S8 power supplies comply with
the following Agency standards:
• NFPA 72 National Fire Alarm Code,
• UL Standard 864, 9th Edition for control units for Fire
Alarm Systems (NAC expander mode).
• UL 1481 Power Supplies for Fire Alarm Systems
(stand-alone mode).
Features
• UL Listed NAC synchronization using System Sensor,
Cooper-Wheelock or Gentex (Commander Series)
appliances.
• Cascade up to ten (10) power supplies (four (4) power
supplies with Gentex) with strobe timing maintained.
• Operates as a sync follower or a sync generator
(default).
• Contains two (2), fully -isolated input/control circuits
energized from FACP notification appliance circuit
(NAC expander mode) or jumpered permanently on
(stand-alone mode).
• Configured to internally house addressable SLC control
module for alarm activation.
• Four (4) Class B (Style Y) or four (4), Class A (Style Z)
(with ZNAC-4 Module) notification appliance circuits.
• 6.0A or 8.0A (depending on model) full load output
(3.0A maximum per circuit) in NAC expander mode
(UL Standard 864).
• 4.0A or 6.0A continuous output in stand-alone mode
(UL Standard 1481).
An ISO 9000-2000 Company
SIGNALING
UOXX.S6677 7315-1637:102
UTRZ.S6677
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-60062 Rev. A1 page 1 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118