欢迎访问ic37.com |
会员登录 免费注册
发布采购

IF602VE-126 参数 Datasheet PDF下载

IF602VE-126图片预览
型号: IF602VE-126
PDF下载: 下载PDF文件 查看货源
内容描述: 模拟寻址控制面板带有语音疏散 [Analog Addressable Control Panel with Voice Evacuation]
分类和应用:
文件页数/大小: 4 页 / 99 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号IF602VE-126的Datasheet PDF文件第2页浏览型号IF602VE-126的Datasheet PDF文件第3页浏览型号IF602VE-126的Datasheet PDF文件第4页  
600 Series
IdentiFlex 602VE
Description
The IdentiFlex 602 with Voice Evacuation (IF602VE) is ide-
ally suited for small- to medium-sized installations of com-
mercial, institutional, and industrial life-safety applications.
The IF602VE offers all the features of today’s most
advanced life safety systems. The integration of analog
and addressable hardwired circuits allows system engi-
neers to customize panels and maximize efficiency for a
given application.
The IF602VE can monitor and control up to 252 intelligent
analog addressable input/output points. The interactive
operator’s display uses LED prompting for ease of pro-
gramming and user operation. The alphanumeric display
and keypad simplify field programming, or download pro-
gramming from a Windows
®
-based application.
State-of-the-art, single-channel (25 watts) voice evacuation
is built into the IF602VE panel. It is expandable to 50 watts.
With zone splitting, up to 50 watts of audio power can be
divided into as many as eight speaker circuits (zones), and
full manual control with status indication is included via a
separate keypad.
With the IF602VE, up to five field-programmable messages
(up to 60 seconds total message duration) can be recorded
with an integral microphone or from an external audio
source. The panel provides full supervision in both active
alarm and standby conditions; the amplifier outputs, field
wiring, message generator, all tone generators, and the
microphone are all supervised.
The IF602VE’s housing was designed to be both aestheti-
cally pleasing and functionally sound. The cabinet is
designed to fit between studs for semi-flush mounting. The
compact design and key-activated dead-front construction
enables secure routine maintenance of the system. Access
to system function keys is limited by a key switch. Multiple
levels of password protection prohibit unauthorized use.
The circuit boards are mounted on a removable chassis,
and are designed with pluggable terminal strips for ease of
installation and service.
SmartStart™ and SmartLink™ are trademarks of Honeywell International Inc.
Microsoft
®
Windows
®
is a registered trademark of Microsoft Corporation.
g2497ph1.jpg
Analog Addressable Control Panel
with Voice Evacuation
Feature
IF602VE
• One or two Signaling Line Circuits (SLC), up to 252
points.
• Polarity-insensitive SLC circuit wiring.
• SmartStart™ self-programming logic.
• Downloadable or front-panel programmable.
• Password protected.
• Approved for Agent Releasing and Supervisory Service.
• Fully digital SLC protocol.
• SmartLink™ peer-to-peer networkable.
• 1000-event history log.
• Automatic drift compensation.
• Coded signaling capability.
• Adjustable sensor sensitivity and temperature settings.
• Supervisory service.
• Style 6 (Class A) or Style 4 (Class B) SLC.
• Four Style Y (Class B), or two Style Z (Class A)
notification appliance circuits (NACs).
• Semi-flush mounting (between 16" studs).
• 160-character display.
• UDACT compatible.
• Built-in strobe and horn synchronization.
An ISO 9000-2000 Company
SIGNALING
FM
APPROVED
S521
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2497 Rev. A page 1 of 4
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118