欢迎访问ic37.com |
会员登录 免费注册
发布采购

MMI-6SF 参数 Datasheet PDF下载

MMI-6SF图片预览
型号: MMI-6SF
PDF下载: 下载PDF文件 查看货源
内容描述: 多模6区段接口模块 [Multi-Mod 6 zone interface module]
分类和应用:
文件页数/大小: 2 页 / 103 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号MMI-6SF的Datasheet PDF文件第2页  
Velociti Series
MMI-6SF
Description
The Velociti™ Series, multi-mod six zone interface
module (MMI-6SF) provides six (6), Style B (Class
B) or three (3), Style D (Class A) supervised initiat-
ing device circuits (IDC) suitable for use with
U. L. Listed conventional 2-wire smoke detectors
as well as any normally open contact device.
The Velociti
TM
Series use a communication proto-
col that substantially increases the speed of com-
munication between the sensors and certain FCI
analog addressable fire alarm controls. These de-
vices operate in a grouped fashion. If one of the
devices in the group has a status change, the
panel’s microprocessor stops the group poll and
concentrates on the single device. The net effect is
response speed up to five times greater than ear-
lier designs.
The MMI-6SF connects to the signaling line circuits
(SLC) of the FCI analog addressable series fire
alarm control panels. Each of the MMI-6SF initiat-
ing device circuits occupies its own address on the
system’s SLC allowing each to be fully programma-
ble in its control-by-event sequence of operation.
The address of the first initiating device circuit is
set with a pair of rotary dials. Each remaining cir-
cuit is automatically assigned to its own subse-
quent address. The MMI-6SF module includes an
address disable jumper matrix to allow a maximum
of two unused addresses to be turned off to free
these addresses for other purposes. An additional
pair of jumpers selects either Style B or Style D
circuit configurations.
Each circuit has its own status LED that flashes to
indicate proper polling and lights steadily when the
output has been activated.
Multi-Mod Six Zone
Interface Module
MMI-6SF
Features
Each MMI-6SF module provides six (6), Style B
(Class B) or three (3), Style D (Class A) individually
addressable individually programmable initiating
device circuits.
Suitable for use with U. L. Listed, compatible 2-wire
conventional smoke sensors and normally open
contact devices.
Removable wiring terminal blocks allow ease of
installation and servicing terminal.
Blocks can accommodate 12 to 18 AWG wire.
Flexible jumper configuration feature allowing
one or two monitoring circuit addresses to be
disabled.
Individual LED indicators*.
Ideal for retrofit applications.
As many as thirty-six (36), initiating device circuits in
one 12” x 24” x 6.5” cabinet.
Two (2), mounting cabinets available for two (2),
(MBB-2 cabinet) to six (6), (MBB-6 cabinet) units.
Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm.*
Note: *Only the red LED is operative in panels that do not oper-
ate in Velociti™ mode.
An ISO 9001-2000 Company
Velociti
and E3 Series
are trademarks of Fire Control Instruments.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
www.gamewell.fci.com
9020-0633 Rev. B page 1 of 2
©2006 Gamewell-FCI. All rights reserved.