600 Series
MPS-8 and APS-8
Description
Gamewell-FCI’s 600 Series power supplies, the MPS-8
and the APS-8, have been developed for today’s critical
power requirements that demand high efficiency and out-
standing reliability. The extensive use of audio/visual
devices for ADA signaling and UL 1971 notification appli-
ances has increased the amount of power the fire alarm
control panel (FACP) must supply. The MPS-8 and APS-8
supply that power with margins to spare. The MPS-8 Main
Power Supply is controlled by the FACP microprocessor to
maintain adequate voltage levels and output current. The
IF650 can accommodate an additional MPS-8 (expansion
cabinet required) if greater system power or battery charg-
ing is required.
The APS-8 is an Auxiliary Power Supply specifically
designed to provide 8.0 amps of 24 VDC signaling or auxil-
iary power to the system. APS-8 power supplies may be
added to a system as required. The APS-8 does not con-
nect to the MPU bus directly, so it does not impact the num-
ber of input or output modules that may be added to the
system. The APS632-8 is similar to the APS-8 — the
APS632-8 is designed to fit into the IF632’s expansion
cabinet (CAB632-4).
600 Series Power Supplies
gf-2023ph1.wmf
MPS-8
APS-8
Features
MPS-8 Main Power Supply:
8.0 A power supply.
4.0 A system power, 4.0 A signaling power.
Standard with IF632 and IF650 FACPs.
Supervised and controlled by the main FACP CPU.
ADA inrush-tolerant design.
60 AH battery charging capacity.
Automatic high-rate charger.
APS-8 or APS632-8:
Auxiliary Power Supply
8.0 A auxiliary power supply.
Provides 24 VDC signal or auxiliary power.
ADA inrush-tolerant design.
IdentiFlex 632 and IdentiFlex 650 systems support an
unlimited number of auxiliary power supplies.
Operation
The MPS-8 and connected batteries are supervised
through the FACP CPU. In the event of loss of either main
AC or battery power, the FACP CPU will report the trouble
at the operator’s display. The MPS-8 also provides brown-
out detection for the system.
The standard battery charger on the MPS-8 is capable of
charging up to 60 AH batteries.
The APS-8 auxiliary power supply is monitored through its
connection to output modules such as the Universal Signal
Module (USM). Battery standby power for the APS-8 is
supplied through a connection at the MPS-8. The MPS-8,
with the main CPU, manages the secondary power source.
An ISO 9000-2000 Company
SIGNALING
FM
APPROVED
MEA
Approved