PID-95, PID-95P
Description
The Gamewell-FCI PID-95-P addressable point identifica-
tion device is the interface between the non-powered, nor-
mally open, dry-contact devices and Gamewell-FCI’s 600
Series of analog addressable Fire Alarm Control Panels
(FACPs). Point identification devices monitor a single Style
B circuit, and are designed for concealed mounting in an
electrical backbox. The PID-95P can be surface-or-flush
mounted and has a visible LED for alarm/annunciation.
Point Identification Device
Operation
The point identification device connects to the Signaling
Line Circuit (SLC) via two wires. The PID-95 will monitor,
via a two-wire supervised SLC circuit, contact-type devices
such as a waterflow switch or manual station. Upon activa-
tion of the monitored device, the PID-95 will report its
address to the 600 Series FACP via the analog SLC. The
control panel will then activate into all alarm programmed
outputs related to the PID-95.
PID-95P
PID-95
Features
Monitors dry-contact devices.
LED for alarm annunciation.
Supervises DC power in.
Field programmable.
Priority interrupt.
Plate-mounted version available for surface or flush
mounting in 4"
(11 cm)
square, 4.688"
(11.908 cm),
or
double gang boxes.
Programming
The PID-95 is programmed by setting a single DIP switch,
easily accessible on the device’s printed circuit board. The
DIP switch sets the address of the device and the priority
interrupt (DIP SW #8). All other programming is accom-
plished at the FACP through a laptop computer or the con-
trol panel operator’s display.
Standard Application
The PID-95 is the interface between dry-contact type
devices and the SLC of the control panel. The PID-95 is a
means of connecting and identifying monitor points without
the use of conventional input modules at the main control
panel. The use of PID-95s can dramatically reduce the field
wiring required on many projects.
An ISO 9000-2000 Company
SIGNALING
FM
Microsoft Windows is a registered trademark of Microsoft Corporation.
®
®
®
S521
MEA
APPROVED
Approved
7300-1288:147
GAMEWELL-FCI
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2007 Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
CS-2044 Rev. A page 1 of 2