欢迎访问ic37.com |
会员登录 免费注册
发布采购

SS-I 参数 Datasheet PDF下载

SS-I图片预览
型号: SS-I
PDF下载: 下载PDF文件 查看货源
内容描述: 智能寻址插件离子式烟雾探测器 [Intelligent Addressable Plug-In Ionization Smoke Detector]
分类和应用:
文件页数/大小: 2 页 / 93 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号SS-I的Datasheet PDF文件第1页  
Product Line Information
SS-I:
Low-profile intelligent ionization
M02-09-00:
Test magnet with telescope
smoke detector. Must be mounted to one stick.
of the bases listed below.
XR2B:
Detector removal tool. Allows
Bases:
installation and/or removal of SS-I
detector heads from base in high ceiling
SS-B6:
Standard U.S. low-profile base,
installations.
UL Listing.
B501BP:
Standard European flangeless
T55-127-000:
Detector removal tool
without pole.
base, pkg. of 10.
XP-4:
Extension pole for XR2B. Comes
B501BH:
Sounder base, includes B501
in three 5-ft. sections.
base above.
B501BHT:
Same as B501BH, but
Detector Guards:
includes temporal sounder.
NOTE:
The following guards are not UL
B224RB:
Intelligent relay base.
listed with the SS-I detectors. Consult AHJ.
STI 9601:
Low-profile, flush-mount smoke
Accessories:
detector guard, wire.
RA400Z:
Remote LED annunciator. 3 –
32 VDC. Fits U.S. single-gang electrical
STI 9602:
Low-profile, surface-mount,
smoke detector guard, wire.
box.
Supported by SS-B6 and B501
STI 9609:
High-profile, flush-mount, smoke
bases only.
SMK400:
Surface mounting kit provides detector guard, wire.
STI 9605:
High-profile, surface-mount,
for entry of surface wiring conduit.
For
smoke detector guard, wire.
use with B501 base
only.
STI 9604:
Flush-mount heat detector
RMK400:
Recessed mounting kit.
For
guard, wire.
use with B501 base
only.
SMB600:
Surface mounting kit for use
STI 9610:
Surface-mount heat detector
with SS-B6.
guard, wire.
BCK-200B:
Black detector covers, box of
STI-8200-SS:
Flush-mount stainless
10. Use with SS-I.
steel smoke detector guard
M02-04-01:
Test magnet.
STI-8230-SS:
Surface-mount stainless
steel smoke detector guard
Specifications
Size
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base, 6.1"
(15.5 cm) diameter installed in SS-B6
base.
Shipping weight
5.4 oz. (154 g).
Operating temperature
0°C to 49°C (32°F to 120°F).
UL-Listed velocity range:
ION:
0 – 1200 ft./min. (365.76 m/min.).
Relative humidity
10% – 93% noncondensing.
DETECTOR SPACING:
Gamewell recommends spacing detec-
tors in compliance with NFPA 72. In low
airflow applications with smooth ceilings,
space detectors 30 feet (9.144 m). For
specific information regarding detector
spacing, placement, and special applica-
tions, refer to NFPA 72.
System Smoke
Detector Application Guide,
document
A05-1003, is available at
systemsensor.com.
ELECTRICAL SPECIFICATIONS:
Voltage range
15 - 32 volts DC peak.
Standby current (max. avg.)
200 µA @ 24 VDC (without communica-
tion); 300 µA @ 24 VDC (one communi-
cation every 5 seconds with LED
enabled).
LED current (max.)
6.5 mA @ 24 VDC (“ON”).
BASES AVAILABLE:
SS-B6:
6.1" (15.5 cm) diameter.
B501:
4.1" (10.4 cm) diameter.
B501BH or B501BHT:
Sounder base
assembly. Includes B501 base.
B224RB Relay Base:
Screw terminals:
up to 14 AWG (2.0 mm²).
Relay type:
Form-C.
Rating:
2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0
A @ 30 VDC inductive.
Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
B224BI Isolator Base:
Dimensions:
6.2" (15.748 cm) x 1.2" (3.048 cm).
Maximum:
25 devices between isolator
bases.
Wiring Diagrams
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Address dial on back of detector.
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
Page 2 of 2
SS-I