欢迎访问ic37.com |
会员登录 免费注册
发布采购

VSYS9 参数 Datasheet PDF下载

VSYS9图片预览
型号: VSYS9
PDF下载: 下载PDF文件 查看货源
内容描述: 紧急语音疏散 [Emergency Voice Evacuation]
分类和应用:
文件页数/大小: 2 页 / 127 K
品牌: GAMEWELL-FCI [ GAMEWELL-FCI BY HONEYWELL ]
 浏览型号VSYS9的Datasheet PDF文件第1页  
Ordering Information
VSYS1
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX25
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX25-4B
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX50
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX50-4B
voice system
mounted in the cabinet.
IF610-252VE includes main CPU board, display board, keypad,
two-
loop
card, and 6 A power supply; plus
VEX50-4B
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX100-4B
voice system
mounted in the cabinet.
IF610-252VE includes main CPU board, display board, keypad,
two-
loop
card, and 6 A power supply; plus
VEX100-4B
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX200-8B
voice system
mounted in the cabinet.
IF610-252VE includes main CPU board, display board, keypad,
two-
loop
card, and 6 A power supply; plus
VEX200-8B
voice system
mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX25-2A
Class A voice
system mounted in the cabinet.
IF610-126VE includes main CPU board, display board, keypad,
single-loop
card, and 6 A power supply; plus
VEX50-4A
Class A voice
system mounted in the cabinet.
IF610-252VE includes main CPU board, display board, keypad,
two-
loop
card, and 6 A power supply; plus
VEX100-4A
Class A voice
system mounted in the cabinet.
IF610-252VE includes main CPU board, display board, keypad,
two-
loop
card, and 6 A power supply; plus
VEX200-8A
Class A voice
system mounted in the cabinet.
IF610-504VE includes main CPU board, display board, keypad,
four-
loop
card, and 6 A power supply; plus
VEX100-4B
voice system
mounted in the cabinet.
IF610-504VE includes main CPU board, display board, keypad,
four-
loop
card, and 6 A power supply; plus
VEX200-8B
voice system mounted in
the cabinet.
Specifications
Voice evacuation system
Input power
25 watt, 50 watt:
120 VAC, 0.80 A.
100 watt:
120 VAC, 0.60 A.
200 watt:
120 VAC, 1.20 A.
Current
25 watt:
0.18 A standby, 1.00 A
alarm.
50 watt:
0.13 A standby, 1.00 A
alarm.
100 watt:
0.18 A standby, 2.50 A
alarm.
200 watt:
0.36 A standby, 5.00 A
alarm.
Battery charging capabilities
25 watt, 50 watt:
up to 18 AH.
100 watt:
up to 24 AH.
200 watt:
up to 48 AH.
VSYS2
VSYS3
VSYS4
VSYS5
VSYS6
VSYS7
VSYS8
VSYS9
VSYS10
VSYS11
VSYS12
Separate sources of 120 VAC input
power and 24 VDC battery backup
power are used for the Fire Alarm Con-
trol Unit and the Voice Evacuation sys-
tem. AC power source requirements
are determined by adding the amper-
age requirements of the two systems
together. Independent battery backup
calculations must be completed for the
Fire Alarm Control Unit and the Voice
Evacuation system.
Dimensions
Cabinet:
30.0" H x 22.0" W x 5.5" D
(cm: 76.2 H x 55.88 W x 13.97 D)
for all VSYS options.
Battery storage:
6.5" H x 22.0" W x
4.5" D (cm: 16.51 H x 55.88 W x
11.43 D).
Relative humidity
93% noncondensing.
Temperature rating
VSYS14
VSYS15
VSYS16
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472
Phone: 203-484-7161
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
32°F – 120°F (0°C – 49°C).
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Page 2 of 2
VSYS for IF610
CS-2002 09/01/06