Specifications
Ordering Information
F405
Five-zone, 24-volt fire alarm control communicator. Includes
backbox, transformer, technical manual, and frame-and-post
operating instruction sheet.
120 VAC, 100 VA transformer expands NAC power from 3.0
to 5.0 amps.
Five-zone remote annunciator (RZA-5F), mounts to a single-
gang box
(requires ADM-24).
Annunciator driver module (supports SAN-405).
Five-zone relay module, provides contact-by-zone.
Class A converter module. Converts all Class B initiating
device circuits (zones) to Class A.
Printer interface module, provides an EIA-232 printer output.
Includes cable, DB9F and DB25 adapter.
Contains programming software for Windows®-based PC
computer
(cable not included).
DACT phone cord, 7 feet (2.134 m) long
(two required).
Battery backbox, required for batteries over 7 AH.
Trim ring.
Flex 405 Installation and Maintenance Manual.
• Single PC board design using Surface Mount
Technology (SMT).
• Two modular telephone jacks for connection to
RJ31X/modules.
AC power
• 120 VAC, 50/60 Hz, 2.3 A.
Wire size:
minimum 14 AWG
(2.0 mm²) with 600-volt insulation.
• Built-in brownout circuitry, built-in voltmeter.
Communicator
• One line-active indicator for each of two
phone lines.
• “Kiss-Off” signal LED.
• Dual “low telephone voltage detect” circuitry.
• Programmable event codes per each format.
• Up to 62 transmitted events/messages.
Selectable/deselectable transmissions of 62
events.
• Five zones may be configured to five
channels as a slave communicator (channels
are auto-resettable.
Communication formats
Express formats allow complete transaction to
be communicated in under five seconds.
• 20 PPS, 3+1 standard & expanded.
• 20 PPS, 4+1 standard & expanded.
• 20 PPS, 4+2 standard & expanded.
• 4+1 and 4+2 Ademco Express.
Initiating device circuits (zones)
• The Flex 405 includes five programmable
initiating device circuits (zones). Circuits 1, 2, 4,
and 5 are Style B (Class B). Circuit 3 is Style
D (Class A). Use Class A converter module
(P/N
CAC-5F)
to convert Class B IDCs to
Class A.
• Each zone may support two-wire smoke
detectors. Programming options include:
waterflow (silenceable/non-silenceable),
supervisory (standard/auto-reset), pull station,
normally-open-contact device.
• All circuits are power-limited and supervised.
• All circuits allow up to 100 ohms of line
resistance. Use 12 to 18 AWG wire (3.1 to
0.78 mm²).
Notification appliance circuits
• Two Style Z/Y (Class A/B) @ 2.5 A each.
• All circuits are fully power-limited
and meet UL power-limiting requirements.
Auxiliary outputs
• Resettable four-wire smoke detector power @
300 mA. Non-resettable power @ 300 mA.
• Integral Form-C Alarm and Trouble relays.
• Relay drivers for supervisory and
communication fail.
Cabinet specifications
• The compact cabinet can be surface- or semi-
flush-mounted.
• Knockouts on the top, sides, and back
provide ease of wire entry.
Dimensions, Door:
15.219” high x 14.219” wide
(38.655 cm H x 36.115 cm W).
Backbox:
15.0”
high x 14.5” wide x 3.0” deep (38.1 cm H x
36.83 cm W x 7.62 cm D).
Trim ring (P/N
TR-
1-R):
18.125” high x 17.62” wide (46.038 cm H
x 44.755 cm W).
Page 2 of 4
Flex 405
CS-2405 09/01/06
XRM-24
SAN-405
ADM-24
RM-5F
CAC-5F
PRT-24
PK-CD
MCBL-7
BB-17F
TR-3-R
52223