GOA9xx24
THREE PHASE AC-SWITCH
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 500V
RMS OUTPUT CURRENT 2400 A
GOA94024
Line to line voltage
GOA95024
500 V
400 V
Characteristic
I
RMS
V
INS
(rms)
RMS output current
Insulation voltage
Conditions
Value
2000 A
3000 V
Value
2000 A
3000 V
THYRISTOR CHARACTERISTICS
V
GT
I
GT
dV/dt
V
RRM
Gate trigger voltage
Gate trigger current
Critical rate of rise off-state voltage
Blocking Voltage
T
j
= 25 °C, V
D
= 5 V
T
j
= 25 °C, V
D
= 5 V
Tj= 125 °C
Tj = 125 °C
3 V
300 mA
1000 V/us
1200 V
3 V
300 mA
1000 V/us
1600 V
FUSE TYPE 2 X SIBA 2068132.1400
V
NF
I
NF
P
VF
I²t
Rated voltage
Rated current
Power loss
Total I t
2
690 V
1100 A
At rated current
At 660 V
147 W
1750 kA s
2
690 V
1100 A
147 W
2
1750 kA s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max
Tstg
Max amb. op. Temp.
Storage temperature
500 mm
275 mm
855 mm
140 kg
40 °C
-40/60 °C
500 mm
275 mm
855 mm
140 kg
40 °C
-40/60 °C
Document GOA9xx24T001