Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOA9xx03C
THREE PHASE AC-SWITCH
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Compact design
LINE VOLTAGE UP TO 500V
RMS OUTPUT CURRENT 300A
GOA94003C GOA95003C
Line to line voltage
400
500
Characteristic
I
RMS
V
INS
(rms)
RMS output current
Insulation voltage
Conditions
Value
300 A
3000 V
Value
300 A
3000 V
THYRISTOR TRIGGERING CHARACTERISTICS
V
GT
I
GT
dV/dt
VRRM
Gate trigger voltage
Gate trigger current
Critical rate of rise off-state voltage
Blocking Voltage
T
j
= 25 °C, V
D
= 5 V
T
j
= 25 °C, V
D
= 5 V
Tj= 125 °C
Tj = 125 °C
3 V
300 mA
1000 V/us
1200 V
3 V
300 mA
1000 V/us
1600 V
FUSE TYPE SIBA 2062432.450
V
NF
I
NF
P
VF
I²t
Rated voltage
Rated current
Power loss
Total I t
2
690 V
450 A
At rated current
At 660V
75 W
110 kA2s
690 V
450 A
75 W
110 kA2s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max
Tstg
Max amb. op. Temp.
Storage temperature
400 mm
340 mm
500 mm
30 Kg
40 °C
-40/ +60 °C
450 mm
340,5 mm
500 mm
30 Kg
40 °C
-40/ +60 °C
Document GOA9xx03CT002