Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOB9xx15
Bi-DIRECTIONAL
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 690V
DC OUTPUT CURRENT 1500A
GOB94015
Line to line voltage
GOB95015 GOB96015
500 V
690 V
400 V
Characteristic
I
DC
V
INS
(rms)
DC output current
Insulation voltage
Conditions
Value
1500 A
3000 V
Value
1500 A
3000 V
Value
1500 A
3000 V
THYRISTOR CHARACTERISTICS
V
GT
I
GT
dV/dt
VRRM
Gate trigger voltage
Gate trigger current
Critical rate of rise off-state voltage
Blocking Voltage
T
j
= 25 °C, V
D
= 5 V
T
j
= 25 °C, V
D
= 5 V
Tj= 125 °C
Tj = 125 °C
3 V
300 mA
1000 V/us
1200 V
3 V
300 mA
1000 V/us
1600 V
3 V
300 mA
1000 V/us
2200 V
FUSE TYPE SIBA 2067132.900 / 2078132.900
V
NF
I
NF
P
VF
I²t
Rated voltage
Rated current
Power loss
Total I
2
t
At rated current
690 V
900 A
111 W
2
950 kA s
690 V
900 A
111 W
2
950 kA s
1250 V
900 A
140 W
2
1300 kA s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max
Tstg
Max amb. op. Temp.
Storage temperature
500 mm
275 mm
855 mm
130 kg
40 °C
-40/60 °C
500 mm
275 mm
855 mm
130 kg
40 °C
-40/60 °C
500 mm
375 mm
1405 mm
130 kg
40 °C
-40/60 °C
Document GOB9xx15T002