Green Power Solutions srl
Via Greto di Cornigliano 6R - 16152 Genova , Italy
Phone: +39-010-659 1869
Fax: +39-010-659 1870
Web: www.gpsemi.it
E-mail: info@gpsemi.it
GOG91K14
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 1000V
DC OUTPUT CURRENT 1450 A
GOG91K14
Line to line voltage
1000 V
Characteristic
I
DC
V
INS
(rms)
DC output current
Insulation voltage
Conditions
1 min. (IEC 1461.1)
Value
1450 A
3000 V
THYRISTOR CHARACTERISTICS
V
GT
I
GT
dV/dt
VRRM
Gate trigger voltage
Gate trigger current
Critical rate of rise off-state voltage
Blocking Voltage
T
j
= 25 °C, V
D
= 5 V
T
j
= 25 °C, V
D
= 5 V
Tj= 125 °C
Tj = 125 °C
3 V
400 mA
1000 V/us
2800 V
FUSE TYPE: 2 x SIBA 2078132.800
V
NF
I
NF
P
VF
I²t
Rated voltage
Rated current
Power loss
Total I t
2
1250 V
800 A
At rated current
At 1000 V
135 W
2
1070 kA s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max
Tstg
Max amb. op. Temp.
Storage temperature
590 mm
270 mm
850 mm
70 kg
40 °C
-40/60 °C
Document GOG91K14T001