GOG9xx24
THREE PHASE AC-DC BRIDGE
Fuse protection
Blown fuse indicators with microswitch
Over temperature switches
Fan loss detection circuit
Snubber for SCR's protections
Extractible stacks for easy field service
LINE VOLTAGE UP TO 500V
DC OUTPUT CURRENT 2400A
GOG94024 GOG95024
Line to line voltage
400
500
Characteristic
I
DC
V
INS
(rms)
DC output current
Insulation voltage
Conditions
Value
2400 A
3000 V
Value
2400 A
3000 V
Value
THYRISTOR CHARACTERISTICS
V
GT
I
GT
dV/dt
V
RRM
Gate trigger voltage
Gate trigger current
Critical rate of rise off-state voltage
Blocking Voltage
T
j
= 25 °C, V
D
= 5 V
T
j
= 25 °C, V
D
= 5 V
Tj= 125 °C
Tj = 125 °C
3 V
300 mA
1000 V/us
1200 V
3 V
300 mA
1000 V/us
1600 V
FUSE TYPE SIBA 2068132.1400
V
NF
I
NF
P
VF
I²t
Rated voltage
Rated current
Power loss
Total I t
2
690 V
1400 A
At rated current
At 660V
161 W
2200 kA s
2
690 V
1400 A
161 W
2
2200 kA s
MECHANICAL AND THERMAL CHARACTERISTICS
Width
Depth
Height
Mass
Ta max
Tstg
Max amb. op. Temp.
Storage temperature
620 mm
360 mm
855 mm
100 kg
40 °C
-40/60 °C
620 mm
360 mm
855 mm
100 kg
40 °C
-40/60 °C
Document GOG9xx24T001