欢迎访问ic37.com |
会员登录 免费注册
发布采购

70G-OAC5AMA 参数 Datasheet PDF下载

70G-OAC5AMA图片预览
型号: 70G-OAC5AMA
PDF下载: 下载PDF文件 查看货源
内容描述: 手动覆盖输出模块 [Manual Override Output Modules]
分类和应用:
文件页数/大小: 2 页 / 104 K
品牌: GRAYHILL [ GRAYHILL, INC ]
 浏览型号70G-OAC5AMA的Datasheet PDF文件第2页  
Manual Override Output Modules
FEATURES
• Integral Three Position Manual
On/Manual Off and Automatic
Control Toggle Switch
• Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
• UL, CSA Certified
• Optical Isolation
• G5 Modules Provide Replaceable
5x20 mm Glass Fuse
• Built-in Status LED
CIRCUITRY
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a two
cubic foot sealed enclosure.
4
AC Outputs
+
1
DC Outputs
LOAD
1
LOAD
VAC
LOAD
SNUBBER
2
VDC
VOLTAGE
SPIKE
PROTECTION
LOAD
2
TRIGGER
CIRCUIT
LOAD CURRENT (AMPS)
G5 PACKAGE
DRIVER
CIRCUIT
3
2
+
1
DC CONTROL
Rx
3
OFF
4
5
5
+
DC CONTROL
Rx
3
OFF
4
AUTO
ON
-20˚
0
20˚
40˚
60˚
AMBIENT TEMPERATURE (˚C)
80˚
100˚
AUTO
ON
-40˚
Figure 1
Maximum Peak Surge Current
Versus Surge Duration (AC Outputs)
Information is based on a supply frequency of
60 Hz sinusoidal and a resistive or inductive
load. Application of maximum surge current
may not be repeated until the module
temperature has returned to its steady state
value.
PEAK SURGE CURRENT (AMPERES)
300
200
100
80
60
40
30
20
10
6
4
3
1
1
1
1000
2 3 4 6 10 20 40 60 100
NUMBER OF FULL CYCLES AT 60 HERTZ
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent.
I/O Modules
I/O
12
STA
NDA
RD,
MINI
, G5
OPE
NLI
NE
Figure 2
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois