欢迎访问ic37.com |
会员登录 免费注册
发布采购

HVP400-T050MI 参数 Datasheet PDF下载

HVP400-T050MI图片预览
型号: HVP400-T050MI
PDF下载: 下载PDF文件 查看货源
内容描述: 通用输入谐波校正AC- DC N + 1冗余和有功电流共享外壳箱单和多输出400瓦内部开关 [UNIVERSAL INPUT HARMONIC CORRECTION AC-DC N+1 REDUNDANCY AND ACTIVE CURRENT SHARING ENCLOSURE BOX SINGLE & MULTI-OUTPUT 400 WATTS INTERNAL SWITCHING]
分类和应用: 开关输出元件瞄准线输入元件
文件页数/大小: 2 页 / 270 K
品牌: HITRON [ HITRON ELECTRONICS CORPORTION ]
 浏览型号HVP400-T050MI的Datasheet PDF文件第2页  
H HiTRON
UNIVERSAL INPUT HARMONIC CORRECTION
AC-DC N+1 REDUNDANCY AND ACTIVE CURRENT SHARING
ENCLOSURE BOX SINGLE & MULTI-OUTPUT 400 WATTS
INTERNAL SWITCHING POWER SUPPLIES HVP400 SERIES
FEATURES:
ACCOMMODATE UNIVERSAL AC SOURCES
MEET IEC 61000-3-2 HARMONIC CORRECTION
THIRD-WIRE CURRENT SHARING
OR-ING DIODES FOR N+1 REDUNDANCY
HOT-SWAPPABLE
MEET UNIVERSAL SAFETY STANDARDS
EMI MEET EN 55022 CLASS B
CE MARKING COMPLIANCE
SPECIFICATION
INPUT SPECIFICATION
Input Voltage:
Typ. 90-264Vac with PFC.
Input Connector:
IEC320-3P & On/Off Switch.
Input Frequency:
47-63Hz.
Inrush Current:
30A @230Vac by active inrush
current limiter circuit.
Input Current:
5.8A @ 115Vac, 2.6A @ 230Vac.
Dielectric Withstand:
Meet IEC 60950-1.
EMI:
Meet EN 55022 Class B.
Hold-up Time:
Typ. 7.2-12mS @ 115Vac and
Typ. 35-42mS @ 230Vac.
Power OK Signal:
Available at VO1 & VO2.
Power Factor Correction:
Meet IEC 61000-3-2 Harmonic
Correction. PF typ. 0.92-0.98.
Over Temp. Protection:
By thermostat.
Power Disable:
Pin P3-2/open=shut-down.
Pin P3-2/short=Operation.
Power On LED Indicator:
Installed.
Earth Leakage:
Less than 0.5mA @230Vac.
OUTPUT SPECIFICATION
Output Voltage:
See Ratings Chart.
Output Current:
See Ratings Chart.
Output Connector:
B-S/S-T/Molex MLX5045.
Output Wattage:
Typ. 350-400 watts.
Line Regulation:
Typ. 0.1%.
Load Regulation:
Main VO1 typ. ±1.0%.
Aux.VO2 typ. ±1-2% (Magnetic Amp.).
Aux.VO3 typ. ±3.0% (Couple Common Choke).
Noise & Ripple:
Typ. 1.0% peak to peak.
OVP:
Built-in at main VO1.
Remote Sense:
Available at VO1 & VO2 rail.
Redundancy:
Available for N+1 redundancy operation for
sharing the load.
Current Sharing:
3rd-wire current sharing for VO1
& VO2 rails.
OR-ing Diode:
Installed in VO1,2,3.
Adjustability:
Available at VO1 & VO2.
Output LED Indicator:
Installed in VO1,2,3.
Overload Protection (OLP):
Fully protected against
output overload and short circuit.
Consult the factory for OLP setting.
GENERAL SPECIFICATION
Efficiency:
Typ. 65-70%.
Switching Frequency:
Fixed frequency at 56K Hz.
Circuit Topology:
PWM Fixed Frequency Forward Circuit.
Transient Response:
Output voltage returns in
less than 3mS following
a 25% load change.
Safety Standard:
UL 60950-1/EN 60950-1 Class I.
Hot Swappable:
Available.
Power Density:
2.95 Watts / Cubic Inch.
Operating Temperature:
0 to +50°C under 35 cfm forced
air cooling for full load.
Storage Temperature:
-20 to +85 °C.
Temperature Coefficient:
Typ. 0.04% /°C.
Cooling:
At least required 35 cfm forced cooling air flow
for full load operation.
MTBF:
180,000 hours at full load and 25°C by
MIL-HDBK-217F spec.
Construction:
Enclosure box.
Note: Due to requests in market and advances in technology, specifications subject to change without notification.
In application