WESTCODE
An
IXYS Company
American Square Body Fuse - Long Blades
Size
Voltage
U
N
(V)
Ref:
130US2D0280B
130US2D0315B
130US2D0350B
Current
rating
I
N
(A)
280
315
350
400
450
500
550
630
700
800
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
10
15
21
32.5
44
57
68
105
145
215
Total Clearing
I
2
t @ U
N
(kA
2
s)
60
87
120
190
255
330
390
610
815
1240
Watt Losses
0.8I
N
I
N
36
38
38
40
44.5
49
60
62.5
70
73
72
76
77
80
89
98
120
125
140
146
Tested
Interrupting
rating
1300V
2
130US2D0400B
130US2D0450B
130US2D0500B
130US2D0550B
100kA @1300V
1200V
1100V
120US2D0630B
110US2D0700B
110US2D0800B
150kA @ 1200V
150Ka @ 1100V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 7V 1-5
Size
Voltage
U
N
(V)
Ref:
130US3D0315B
130US3D0350B
130US3D0400B
Current
rating
I
N
(A)
315
350
400
450
500
550
630
700
800
900
1000
Pre-arcing
I
2
t @ 1 ms
I
2
t
p
(kA
2
s)
12
17
25
35.5
44
57
84
110
190
250
370
Total Clearing
I
2
t @ U
N
(kA
2
s)
68
100
145
205
255
330
485
640
1090
1440
2130
Watt Losses
0.8I
N
I
N
42
43
46.5
50
56
60
66
73
74
85
87
84
86
93
100
112
120
132
146
148
170
168
Tested
Interrupting
rating
1300V
3
130US3D0450B
130US3D0500B
130US3D0550B
130US3D0630B
130US3D0700B
100kA @ 1300V
1200V
1100V
900V
120US3D0800B
110US3D0900B
100US3D1000B
150kA @ 1200V
150kA @ 1100V
150kA @ 900V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Micro switch reference : MS 7V 1-5
Electrical Characteristics:
Times vs current characteristics
The curves shown on page 4 indicate the pre-arcing time for each rated current as a function of RMS
value of pre-arcing current I:
-
Tolerances on this current ± 8%
-
Beyond 30 sec, small overloads must be eliminated by another device.
-
Curve CC’ represents the maximum times taken by the associated device to clear small overloads; only its
horizontal line is represented.
Its oblique line must be plotted according to sketch in top right corner:
-
The intersection of the fuse and CC’ curves indicates the minimum breaking current I
pm
of the fuse.
Data Sheet. 130USxDxxxxB
Issue 1
Page 3 of 8
March, 2005