AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
I
PN
= 10 .. 400 A
Preliminary
Electrical data
Primary Nominal Current
I
PN
(A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
R
L
V
C
V
d
Analogue Output Signal
V
OUT
(V)
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
0-5V or 0-10V
Type
Features
•
VFD and SCR waveforms current
measurement
•
True RMS output
•
Split core type
•
5V & 10V switch selectable voltage
output.
•
DIN mounting & Panel mounting
•
Eliminates insertion loss
•
Switch selectable ranges
APR 50 B10
APR 100 B10
APR 200 B10
APR 400 B10
≥
10
kΩ
+24 ±5% V DC
5
kV
18
V
Load resistance
Supply voltage
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
Limitation of voltage output
Advantages
•
Large aperture for cable up to Ø18mm
Accuracy-Dynamic performance data
•
High isolation between primary and
secondary circuits
< ±1
% of
I
PN
< ±0.5 % of
I
PN
< ±0.5 % of
I
PN
±1
mV/K
±0.1
%/K
< 1000
ms
10 .. 6000
Hz
•
Easy to mount
ε
X
L
V
OE
V
OT
TC
ε
G
t
r
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
Linearity (0 .. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Thermal drift of
V
OE
Thermal drift of the gain (% of reading)
Response time @ 90% of
I
P
Frequency bandwidth (-3 dB)
Applications
•
VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
•
SCR Controlled Loads:
Acurate measurement of phase angle
fired or burst fired (time proportioned)
SCRs. Current measurement gives
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Reliable isolation according to EN50178, EN61010
Creepage distance
EMC in accordance with EN50082-2
Plastic according to UL94V0, CTI 1
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
300
V AC
>
5.5
mm
faster response than temperature
measurement.
•
Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Notes :
Installation and maintenance should be done with power supply disconnected.
030708/0
LEM Components