AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). Switch selectable
ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
I
PN
= 10 .. 400 A
Electrical data
Primary Nominal Current
I
PN
(A.t.RMS)
10,25,50
50,75,100
100,150,200
200,300,400
Analogue Output Signal
V
OUT
(V)
0-5V
0-5V
0-5V
0-5V
or
or
or
or
0-10V
0-10V
0-10V
0-10V
Type
APR
APR
APR
APR
50 B10
100 B10
200 B10
400 B10
Features
•
VFD and SCR waveforms current
measurement
•
True RMS output
•
Split core type
•
5V & 10V switch selectable voltage
output
•
DIN mounting & Panel mounting
•
Eliminates insertion loss
•
Switch selectable ranges
R
L
V
C
I
C
Load resistance
Supply voltage
Current Consumption
Limitation of voltage output (0-10V)
Limitation of voltage output (0-5V)
Overloaded input current
≥
10
kΩ
+24 ±5% V DC
< 30
mA
14
V
7
V
no limitation
Accuracy-Dynamic performance data
X
ε
L
V
OE
V
OT
TC
ε
G
t
r
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
Linearity (0 .. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Thermal drift of
V
OE
Thermal drift of the gain (% of reading)
Response time @ 90% of
I
P
Frequency bandwidth (±1%)
< ±1
% of
I
PN
< ±0.5 % of
I
PN
< ±0.5 % of
I
PN
±1
mV/K
±0.1
%/K
< 400
ms
30 .. 6000 Hz
Advantages
•
Large aperture for cable up to
Ø18mm
•
High isolation between primary and
secondary circuits
•
Easy to mount
General data
T
A
T
S
m
dCp
dCl
CTI
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
Creepage distance
Clearance distance
Comparative tracking index (Group I)
UL94 classification
-20 .. +60
°C
-20 .. +85
°C
90
g
IP20
5.5
mm
5.5
mm
600
V
V0
Applications
•
VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
•
SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
•
Switching Power Supplies and
Insulation category
V
b
Rated Voltage
300
with IEC 61010-1 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
R.m.s. voltage for AC insulation test, 50Hz, 1mn
5
R.m.s. voltage for partial discharge extinction @ 10pC 1.5
Peak impulse withstand voltage 1.2/50µs
6.1
If insulated cable is used for the primary circuit, the voltage category
could be improved with the following table :
Cable insulation (primary)
Category
HAR 05
600V CAT III
HAR 07
1000V CAT III
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
V
V
d
V
e
V
w
kV
kV
kV
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
041029/3
Notes :
Installation and maintenance should be done with power supply disconnected.
LEM Components