Current Transducer CT 5 .. 25-T
Isolation characteristics
V
d
V
W
dCp
dCl
CTI
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Impulse withstand voltage 1.2/50 µs
6
> 9.5
Min
104.5
104.5
225
kV
kV
Creepage distance
Clearance distance
Comparative Tracking Index (Group III b)
5)
mm
mm
Application examples
According to EN 50178 and IEC 61010-1 standards
and following conditions :
•
Over voltage category OV 3
•
Pollution degree PD2
•
Non-uniform field
EN 50178
dCp, dCI,
V
W
Single isolation
Reinforced isolation
Rated isolation voltage
1000 V
600 V
IEC 61010-1
Nominal voltage
1000 V
600 V
Note :
5)
Between M5 screws and M5.
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer's
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.