欢迎访问ic37.com |
会员登录 免费注册
发布采购

DHR400C10 参数 Datasheet PDF下载

DHR400C10图片预览
型号: DHR400C10
PDF下载: 下载PDF文件 查看货源
内容描述: AC / DC电流传感器 [AC/DC Current transducer]
分类和应用: 传感器
文件页数/大小: 3 页 / 856 K
品牌: LEM [ LEM ]
 浏览型号DHR400C10的Datasheet PDF文件第2页浏览型号DHR400C10的Datasheet PDF文件第3页  
AC/DC Current transducer DHR-C10
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement). True RMS 0-10V
voltage output.
I
PN
= 100..1000 A
Electrical data
Primary Nominal
DC & AC Current
I
PN
(A.t.RMS)
100
200
300
400
500
600
1000
Primary AC Current
Max. Peak Value
I
P
(A)
(
*
)
600
600
1000
1000
1800
1800
1800
Output voltage
(Analog)
V
OUT
(VDC)
0-10
0-10
0-10
0-10
0-10
0-10
0-10
Type
Features
VFD and SCR waveforms current
measurement
True RMS output
Panel mounting
Eliminates insertion loss
Insulated plastic case recognized
according to UL94-V0
DHR 100 C10
DHR 200 C10
DHR 300 C10
DHR 400 C10
DHR 500 C10
DHR 600 C10
DHR 1000 C10
R
L
V
C
I
C
V
SL
Î
P
Load resistance
Supply voltage
Current Consumption
Output voltage limitation (0-10V)
Overload capability (Ampere Turns)
10
kΩ
+ 20 .. 50 V DC
30
mA
< 14
V
30000
A.t
Advantages
Large aperture for cable up to
Ø32mm
High isolation between primary and
secondary circuits
Easy installation
Performance data
X
ε
L
V
OE
TCV
OE
TCV
OUT
t
r
BW
Accuracy @
I
PN
,
T
A
= 25°C (excluding offset)
Linearity error (1% of
I
PN
.. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Temperature coefficient of
V
OE
( 0..+60 °C)
(-40..+70 °C)
Temperature coefficient of
V
OUT
(% of reading)
Response time tp 90% of
I
PN
step
Frequency bandwidth (±1dB)
< ± 1 % of
I
PN
< ± 1.0 % of
I
PN
< ± 1.0 % of
I
PN
± 2.0
mV/K
± 4.0
mV/K
± 0.1
%/K
< 150
ms
DC 20..6000Hz
Applications
VFD Controlled Loads
VFD output indicates how the motor
and attached load are operating.
SCR Controlled Loads
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
General data
T
A
T
S
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
- 40 .. + 70
- 40 .. + 85
260
IP20
°C
°C
g
measurement gives faster
response than temperature
measurement.
Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most
Note :
* The Max. Peak AC Current is the highest peak level of the primary signal that is
taken into account for accurate True RMS calculation. Yet the device is designed for
maximum continuous True RMS value equal to I
PN
, whereas the output is limited by
the above specified output limitation.
( )
accurate way to measure power
supply or ballast input power.
Application domain
Energy and Automation
Page 1/3
061128/14
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com