DC Current transducer DK-B5/10
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with voltage output.
I
PN
= 50..400A
Electrical data
Primary Nominal Current
I
PN
(A.t)
50,75,100
100,150,200
150,225,300
200,300,400
50,75,100
100,150,200
150,225,300
200,300,400
V
c
R
L
V
d
f
I
c
Supply voltage
Load resistance (max)
Isolation voltage
Frequency
Current consumption (max)
Analogue Output Signal
1)
V
OUT
(V)
0-5
0-5
0-5
0-5
0-10
0-10
0-10
0-10
22-26
250
3000
DC
100
Type
Features
•
DC Measurement
•
Split core box
•
Voltage output
•
Jumper selectable ranges
•
Panel mounting
•
Extended measuring range
DK 100 B5
DK 200 B5
DK 300 B5
DK 400 B5
DK 100 B10
DK 200 B10
DK 300 B10
DK 400 B10
V AC/ DC
kΩ
V AC
mA
Advantages
•
Large aperture
•
High isolation between primary and
secondary circuits
•
Easy to mount
•
No insertion losses
Applications
•
Battery Banks
- Monitors load current.
- Monitors charging current.
- Verifies operation.
•
Transportation
Measures traction power or auxiliary
loads.
•
Electric Heating Elements
Faster response than temperature
sensors.
Accuracy - Dynamic performance data
X
ε
L
t
r
Accuracy @ I
PN
, T
A
=25°C
Linearity
Response time @ 90% of I
PN
±
1
±
0.75
< 300
%
%
mS
General data
T
A
T
S
m
Ambient operating temperature (0-95% RH)
Ambient storage temperature
Mass
- 20 .. + 50
- 20 .. + 85
120
°C
°C
g
Options on request
•
DIN mounting
Note :
1)
For 0-3 V output model, no saturation output up to 3.5 V
for 0-5 V output model, no saturation output up to 5.75 V
and for 0-10 V output model, no saturation output up to 11.5 V
040405/5
w w w .lem.com
LEM Components