欢迎访问ic37.com |
会员登录 免费注册
发布采购

DK300B5 参数 Datasheet PDF下载

DK300B5图片预览
型号: DK300B5
PDF下载: 下载PDF文件 查看货源
内容描述: 直流电流变送器 [DC Current transducer]
分类和应用:
文件页数/大小: 2 页 / 276 K
品牌: LEM [ LEM ]
 浏览型号DK300B5的Datasheet PDF文件第2页  
DC Current transducer DK-B5/10
A split core transducer for the electronic measurement DC current,
with galvanic isolation between the primary (High power) and the
secondary circuits (Electronic circuit) with voltage output.
I
PN
= 50..400 A
Electrical data
Primary Nominal Current
I
PN
(A.t)
50,75,100
100,150,200
150,225,300
200,300,400
50,75,100
100,150,200
150,225,300
200,300,400
V
c
R
L
V
b
V
d
f
I
c
Supply voltage
Load resistance
Rated voltage (CAT
III,
PD2)
Isolation voltage
Frequency
Current consumption (max)
Analogue Output Signal
1)
Type
V
OUT
(V)
0-5
0-5
0-5
0-5
0-10
0-10
0-10
0-10
DK 100 B5
DK 200 B5
DK 300 B5
DK 400 B5
DK 100 B10
DK 200 B10
DK 300 B10
DK 400 B10
20-50
22-38
50 .. 250
150
3000
DC
100
RoHs
Date Code
planned
planned
planned
planned
MAY 2006
MAY 2006
planned
planned
V DC
V AC
kΩ
V AC
V AC
mA
Features
DC Measurement
Split core box
Voltage output
Jumper selectable ranges
Panel mounting
Extended measuring range.
Advantages
Large aperture
High isolation between primary and
secondary circuits
Easy to mount
No insertion losses.
Accuracy - Dynamic performance data
X
Accuracy @ I
PN
, T
A
=25°C
DK 300 BXX
DK 400 BXX
ε
L
t
r
Linearity error
Response time @ 90% of I
PN
±
1
±
1.5
±
2
±
0.75
< 300
%
%
%
%
mS
Applications
Battery Banks
- Monitors load current.
- Monitors charging current.
- Verifies operation.
Transportation
Measures traction power or auxiliary
loads.
Electric Heating Elements
Faster response than temperature
sensors.
General data
T
A
T
S
m
Ambient operating temperature (0-95% RH)
Ambient storage temperature
Mass
Protection type
Safety
EMC
- 20 .. + 50
- 20 .. + 85
120
IP 20
IEC 61010-1
EN 61326
2)
°C
°C
g
Options on request
DIN mounting.
Notes :
1)
For 0-3 V output model, no saturation output up to 3.5 V for 0-5 V output
model, no saturation output up to 5.75 V and for 0-10 V output model, no
saturation output up to 11.5 V
2)
For IEC 61000-4-3, IEC 61000-4-6 and IEC 61000-4-4 Criterion B :
temporary impairment to operational behavior.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060616/9
page 1/2
LEM
www.lem.com