欢迎访问ic37.com |
会员登录 免费注册
发布采购

HTA600-S 参数 Datasheet PDF下载

HTA600-S图片预览
型号: HTA600-S
PDF下载: 下载PDF文件 查看货源
内容描述: 电流传感器HTA 100 〜1000 -S [Current Transducer HTA 100~1000-S]
分类和应用: 传感器
文件页数/大小: 2 页 / 84 K
品牌: LEM [ LEM ]
 浏览型号HTA600-S的Datasheet PDF文件第2页  
Current Transducer HTA 100..1000-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
I
PN
= 100 A
Electrical data
Primary nominal
r.m.s. current
I
PN
(A)
100
200
300
400
500
600
1000
Primary current
measuring range
I
P
(A)
± 300
± 600
± 900
± 1000
± 1000
± 1000
± 1000
Type
HTA 100-S
HTA 200-S
HTA 300-S
HTA 400-S
HTA 500-S
HTA 600-S
HTA 1000-S
Features
Open loop transducer using Hall
Effect
Panel mounting - Horizontal or
Vertical
Insulated plastic case to UL 94-V0.
Î
P
V
OUT
R
L
V
C
I
C
V
b
V
d
R
is
Overload capacity (Ampere Turns)
Analogue output voltage @ ±
I
PN
Load resistance
T
A
= 0 .. + 70°C
T
A
= - 25 .. + 85°C
Supply voltage (± 5 %)
Current consumption (max)
Rms rated voltage
1)
Rms voltage for AC isolation test, 50 Hz, 1 mn
Isolation resistance @ 500 V
DC
30000
±4
>1
>3
± 15
25
500
3
> 500
A
V
kΩ
kΩ
V
mA
V
kV
MΩ
Advantages
Very good linearity
Very good accuracy
Low temperature drift
Wide frequency bandwidth
Very low insertion losses
High immunity to external
interference
Current overload capability
Low power consumption
Wide dynamic range, 100 to 1000 A
in one package.
Accuracy - Dynamic performance data
ε
X
L
Accuracy
2)
@
I
PN
,
T
A
= 25°C, @ ± 15 V
Linearity
2)
Electrical offset voltage @
I
P
= 0,
T
A
= 25°C
Residual offset voltage @
I
P
= 0
after an overload of 3 x
I
PN
Thermal drift of offset voltage
T
A
= - 25 .. + 85°C
Thermal drift of gain
T
A
= - 25 .. + 85°C
Response time @ 90 % of
I
P
di/dt accurately followed
Frequency bandwidth (- 3 dB)
3)
V
OE
V
OM
V
OT
TC
ε
G
t
r
di/dt
f
±1
± 0.5
Max
± 10
± 10
±1
± 0.05
<3
> 50
DC .. 50
%
%
mV
mV
mV/°K
%/°K
µs
A/µs
kHz
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptable Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards Safety
EMC
Deviation in output when tested to EN 61000-4-6
Deviation in output when tested to EN 61000-4-4
Notes :
1)
2)
3)
- 25 .. + 85
°C
- 25 .. + 85
°C
230
g
EN50178 (1994)
EN50082-2 (1992)
EN50081-1 (1992)
< 10
% of
I
PN
< 10
% of
I
PN
Overvoltage Category III, Pollution Degree 2
Excludes the electrical offset
Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
001107/1
LEM Components