Current Transducers HTB 50 .. 400-P/SP5
and HTB 50 .. 100-TP/SP5
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 50 .. 400 A
Electrical data
Primary nominal
r.m.s. current
I
PN
(A)
50
100
200
300
400
Primary current
measuring range
I
P
(A)
±150
±300
±500
±600
±600
Type
HTB 50-P/SP5, HTB 50-TP/SP5
1)
HTB 100-P/SP5, HTB 100-TP/SP5
1)
HTB 200-P/SP5
HTB 300-P/SP5
HTB 400-P/SP5
Features
•
Hall effect measuring principle
•
Galvanic isolation between primary
and secondary circuit
•
Isolation voltage 2500V
•
Low power consumption
•
Primary bus bar option for 50A and
100A version for ease of connection
V
C
I
C
V
d
R
IS
V
OUT
R
OUT
R
L
Supply voltage (±5 %)
2)
Current consumption
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Isolation resistance @ 500 VDC
Output voltage @ ±
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
Output internal resistance
Load resistance
+12 .. +15
V
<15
mA
2.5
kV
>500
MΩ
V
OE
±1.667
V
100
Ω
≥10
kΩ
Accuracy - Dynamic performance data
Special Features
•
Single power supply from 12V to 15V
ε
X
L
V
OE
V
OH
V
OT
TC
ε
G
t
r
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
<±1
% of
I
PN
Linearity (0 .. ±
I
PN
)
<±1
% of
I
PN
Electrical offset voltage,
T
A
= 25°C
Vc/2±30
mV
Hysteresis offset voltage @
I
P
= 0;
after an excursion of 3 x
I
PN
<±0.5 % of
I
PN
Thermal drift of
V
OE
HTB 50-(T)P/SP5
<±1.0
mV/K
HTB 100-(T)P..400-P/SP5
<±0.5
mV/K
Thermal drift (% of reading)
<±0.05
%/K
Response time @ 90% of
I
P
<3
µs
3)
Frequency bandwidth (-3 dB)
DC .. 50 kHz
Advantages
•
Small size and space saving
•
Only one design for wide current
ratings range
•
High immunity to external
interference.
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass (-TP version)
-25 .. +85
-25 .. +85
<30 (<36)
°C
°C
g
Applications
•
AC variable speed drives
•
Static converters for DC motor drives
•
Battery supplied applications
•
Uninterruptible Power Supplies
(UPS)
•
Switched Mode Power Supplies
(SMPS)
•
Power supplies for welding
applications.
Notes : EN 50178 approval pending
1)
-TP version is equipped with a primary bus bar.
2)
Operating at +12V
≤
Vc < +15V will reduce measuring range.
3)
Derating is needed to avoid excessive core heating at high frequency.
030221/0
LEM Components