Current Transducers HTB 50..400-P/SP5
and HTB 50..100-TP/SP5
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 50 .. 400 A
Electrical data
Primary nominal
current rms
I
PN
(A)
50
100
200
300
400
Primary current
measuring range
I
PM
(A)
±
±
±
±
±
150
300
500
600
600
Type
HTB 50-P/SP5, HTB 50-TP/SP5
1)
HTB 100-P/SP5, HTB 100-TP/SP5
1)
HTB 200-P/SP5
HTB 300-P/SP5
HTB 400-P/SP5
Features
•
Hall effect measuring principle
•
Galvanic isolation between primary
V
mA
kV
MΩ
V
Ω
kΩ
and secondary circuit
•
Isolation voltage 2500V
•
Low power consumption
•
Primary bus bar option for 50A and
100A version for ease of connection
V
C
I
C
V
d
R
IS
V
OUT
R
OUT
R
L
Supply voltage (± 5 %)
2)
Current consumption
Rms voltage for AC isolation test, 50 Hz, 1 min
Isolation resistance @ 500 VDC
Output voltage (Analog) @ ±
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
Output internal resistance
Load resistance
+ 12 .. 15
< 15
2.5
> 500
V
OE
± 1.667
100
≥
10
Special feature
•
Single power supply from 12V to 15V
Accuracy - Dynamic performance data
X
ε
L
V
OE
V
OH
TCV
OE
TCV
OUT
t
r
BW
< ± 0.5 % of
I
PN
< ± 1.0 mV/K
HTB 100-(T)P..400-P/SP5
< ± 0.5
mV/K
Temperature coefficient of
V
OUT
(% of reading)
< ± 0.05 %/K
Response time to 90% of
I
PN
step
<3
µs
Frequency bandwidth (0 .. -3 dB)
3)
DC .. 50
kHz
Accuracy @
I
PN
,
T
A
= 25°C (excluding offset)
Linearity error (0 .. ±
I
PN
)
Electrical offset voltage @
T
A
= 25°C
Hysteresis offset voltage @
I
P
= 0,
after an excursion of 1 x
I
PN
Temperature coefficient of
V
OE
HTB 50-(T)P/SP5
< ± 1 % of
I
PN
< ± 1 % of
I
PN
Vc/2 ± 30 mV
Advantages
•
Small size and space saving
•
Only one design for wide current
ratings range
•
High immunity to external
interference.
Applications
•
AC variable speed drives
•
Static converters for DC motor drives
•
Battery supplied applications
•
Uninterruptible Power Supplies
(UPS)
•
Switched Mode Power Supplies
(SMPS)
•
Power supplies for welding
applications.
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass (-TP version)
- 25 .. + 85 °C
- 25 .. + 85 °C
< 30 (< 36) g
Notes :
1)
-TP version is equipped with a primary bus bar.
2)
Operating at +12V
≤
Vc < +15V will reduce measuring range.
3)
Derating is needed to avoid excessive core heating at high frequency.
Page 1/2
070111/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
www.lem.com