Current Transducers HTB 50 .. 400-P
and HTB 50 .. 100-TP
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 50 .. 400 A
Electrical data
Primary nominal
r.m.s. current
I
PN
(A)
50
100
200
300
400
Primary current
measuring range
I
P
(A)
±150
±300
±500
±600
±600
Type
HTB 50-P, HTB 50-TP
1)
HTB 100-P, HTB 100-TP
1)
HTB 200-P
HTB 300-P
HTB 400-P
Features
•
Hall effect measuring principle
•
Galvanic isolation between primary
and secondary circuit
•
Isolation voltage 2500V
•
Low power consumption
•
Wide power supply: ±12V to ±15V
•
Primary bus bar option for 50A and
100A version for ease of connection
V
C
I
C
V
d
R
IS
V
OUT
R
OUT
R
L
Supply voltage (±5 %)
2)
Current consumption
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn
Isolation resistance @ 500 VDC
Output voltage @ ±
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
Output internal resistance
Load resistance
±12 .. ±15
<±15
2.5
>500
±4
100
≥10
V
mA
kV
MΩ
V
Ω
kΩ
Accuracy - Dynamic performance data
ε
X
L
V
OE
V
OH
V
OT
TC
ε
G
t
r
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
Linearity (0 .. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Hysteresis offset voltage @
I
P
= 0;
after an excursion of 3 x
I
PN
Thermal drift of
V
OE
HTB 50-(T)P
HTB 100-(T)P..400-P
Thermal drift (% of reading)
Response time @ 90% of
I
P
Frequency bandwidth (-3 dB)
3)
<±1
<±1
<±30
% of
I
PN
% of
I
PN
mV
Advantages
•
Small size and space saving
•
Only one design for wide current
ratings range
•
High immunity to external
interference.
<±1
% of
I
PN
<±2.0
mV/K
<±1.0
mV/K
<±0.1
%/K
<3
µs
DC .. 50 kHz
Applications
•
AC variable speed drives
•
Static converters for DC motor drives
•
Battery supplied applications
•
Uninterruptible Power Supplies
(UPS)
•
Switched Mode Power Supplies
(SMPS)
•
Power supplies for welding
applications.
General data
T
A
T
S
m
Ambient operating temperature
-20 .. +80
Ambient storage temperature
-25 .. +85
Mass (-TP version)
<30 (<36)
2 pins of Ø2mm diameter are available on transducer
for PCB soldering.
°C
°C
g
Notes : EN 50178 approval pending
1)
-TP version is equipped with a primary bus bar.
2)
Operating at ±12V
≤
Vc < ±15V will reduce measuring range.
3)
Derating is needed to avoid excessive core heating at high frequency.
030529/7