型号: HY15-P/SP1
PDF下载: 下载PDF文件 查看货源
内容描述: 电流转换器HY 5〜25 -P / SP1 [Current Transducers HY 5 to 25-P/SP1]
分类和应用: 转换器
文件页数/大小: 2 页 / 144 K
品牌: LEM [ LEM ]
 浏览型号HY15-P/SP1的Datasheet PDF文件第2页  
Current Transducers HY 5 to 25-P/SP1
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit) with unipolar power
supply.
I
PN
=
5 .. 25 A
Electrical data
Primary nominal
r.m.s. current
I
PN
(A)
5
10
12.5
15
20
25
Primary current
measuring range
I
P
(A)
±
15
±
30
±
37.5
±
45
±
60
±
75
Primary
conductor
(mm)
Type
Features
HY 05-P/SP1
HY 10-P/SP1
HY 12-P/SP1
HY 15-P/SP1
HY 20-P/SP1
HY 25-P/SP1
0.7
1.1
1.4
1.4
2 x
1.2
1)
2 x
1.4
1)
Hall effect measuring principle
Galvanic isolation between primary
and secondary circuit
Isolation voltage 2500 V~
Compact design for PCB mounting
Low power consumption
Extended measuring range (3 x
I
PN
)
Insulated plastic case recognized
according to UL 94-V0.
V
C
I
C
Î
P
V
d
V
b
R
IS
V
OUT
R
OUT
R
L
Supply voltage (± 5 %)
single
Current consumption
Overload capability (1 ms)
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
R.m.s. rated voltage, safe separation
Isolation resistance @ 500 VDC
Output voltage @ +
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
Output voltage @ -
I
PN
,
R
L
= 10 kΩ,
T
A
= 25°C
Output internal resistance
Load resistance
+5
10
50 x
I
PN
2.5
500
2)
> 1000
2.5
1.5
100
>1
V DC
mA
kV
V
MΩ
V
V
kΩ
Advantages
Easy mounting
Small size and space saving
Only one design for wide current
ratings range
High immunity against external
interference.
Accuracy - Dynamic performance data
ε
X
L
V
OE
V
OH
V
OT
TC
ε
G
t
r
di/dt
f
Accuracy @
I
PN
,
T
A
= 25°C (without offset)
Linearity
3)
(0 .. ±
I
PN
)
Electrical offset voltage,
T
A
= 25°C
Hysteresis offset voltage @
I
P
= 0
after an excursion of 1 x
I
PN
Thermal drift of
V
OE
typ
max
Thermal drift of the gain (% of reading)
Response time @ 90% of
I
P
di/dt accurately followed
Frequency bandwidth
4)
(- 3 dB)
<±2
%
< ± 1 % of
I
PN
< + 2V ± 25 mV
< ± 10
mV
± 1.5
mV/K
±3
mV/K
< ± 0.1
%/K
<5
µs
> 50
A/µs
DC .. 50
kHz
Applications
General purpose inverters
AC variable speed drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched-Mode Power Supplies
(SMPS).
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards
5)
- 10 .. + 80 °C
- 25 .. + 85 °C
< 14
g
EN 50178
Notes :
1)
Conductor terminals are soldered together.
2)
Pollution class 2, overvoltage category III.
3)
Linearity data exclude the electrical offset.