Current Transducer LA 55-P
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
I
PN
=
50 A
16019
Electrical data
I
PN
I
PM
R
M
Primary nominal current rms
Primary current, measuring range
Measuring resistance @
with ± 12 V
with ± 15 V
I
SN
K
N
V
C
I
C
V
d
@ ± 50 A
maxi
@ ± 70 A
maxi
@ ± 50 A
maxi
@ ± 70 A
maxi
50
0 .. ± 70
T
A
= 70°C
T
A
= 85°C
R
M mini
R
M maxi
R
M mini
R
M maxi
10
10
50
50
100
50
160
90
60 95
60
1)
60
1)
135 155
135
2)
135
2)
A
A
Features
•
Closed loop (compensated) current
transducer using the Hall effect
•
Printed circuit board mounting
•
Isolated plastic case recognized
according to UL 94-V0.
Ω
Ω
Ω
Ω
Secondary nominal current rms
Conversion ratio
Supply voltage (± 5 %)
Current consumption
Rms voltage for AC isolation test, 50 Hz, 1 min
50
mA
1 : 1000
± 12 .. 15
V
10
(@ ± 15 V) +
I
S
mA
2.5
kV
Advantages
•
•
•
•
•
•
•
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
•
Current overload capability.
Accuracy - Dynamic performance data
X
Accuracy @
I
PN
,
T
A
= 25°C
L
ε
@ ± 15 V (± 5 %)
@ ± 12 .. 15 V (± 5 %)
Linearity error
Offset current @
I
P
= 0,
T
A
= 25°C
Magnetic offset current
3)
@
I
P
= 0 and specified
R
M
after an overload of 3 x
I
PN
Temperature variation of
I
O
0°C .. + 70°C
- 25°C .. + 85°C
Reaction time @ 10 % of
I
PN
Response time @ 90 % of
I
PN
Step
di/dt accurately followed
Frequency bandwidth (- 1 dB)
± 0.65
± 0.90
< 0.15
Typ
Maxi
± 0.2
± 0.3
± 0.5
± 0.6
%
%
%
mA
mA
mA
mA
ns
µs
A/µs
kHz
I
O
I
OM
I
OT
t
ra
t
r
di/dt
BW
Applications
•
AC variable speed drives and servo
•
•
•
•
•
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
± 0.1
± 0.1
< 500
<1
> 200
DC .. 200
General data
T
A
T
S
R
S
m
Ambient operating temperature
Ambient storage temperature
Secondary coil resistance @
Mass
Standards
1)
2)
3)
T
A
= 70°C
T
A
= 85°C
- 25 .. + 85
- 40 .. + 90
80
85
18
EN 50178: 1997
°C
°C
Ω
Ω
g
Application Domain
•
Industrial.
Notes:
Measuring range limited to ± 60 A
maxi
Measuring range limited to ± 55 A
maxi
Result of the coercive field of the magnetic circuit.
page 1/2
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
070103/11
w w w .lem.com