欢迎访问ic37.com |
会员登录 免费注册
发布采购

CP2000DC54 参数 Datasheet PDF下载

CP2000DC54图片预览
型号: CP2000DC54
PDF下载: 下载PDF文件 查看货源
内容描述: 紧凑型电源线输入: -40至-72伏直流;输出: ± 54伏在2000W ; 5 VDC在4W [Compact Power Line Input: -40 to -72 Vdc; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W]
分类和应用:
文件页数/大小: 8 页 / 170 K
品牌: LINEAGEPOWER [ LINEAGE POWER CORPORATION ]
 浏览型号CP2000DC54的Datasheet PDF文件第1页浏览型号CP2000DC54的Datasheet PDF文件第2页浏览型号CP2000DC54的Datasheet PDF文件第3页浏览型号CP2000DC54的Datasheet PDF文件第4页浏览型号CP2000DC54的Datasheet PDF文件第6页浏览型号CP2000DC54的Datasheet PDF文件第7页浏览型号CP2000DC54的Datasheet PDF文件第8页  
Data Sheet  
Compact Power Line  
CP2000DC54-PE DC/DC Converter  
Software commanded margining overrides the  
hardware set point indefinitely or until the default  
setting is reinstated for example if input power and  
bias power have been removed from the module.  
Status and Control  
The PEM provides two means for monitor/control:  
analog or I2C.  
Details of analog controls are provided in this data  
sheet under Signal Definitions. Lineage Power will  
provide separate application notes on the I2C  
protocol for users to interface to the CPL PEMs.  
Contact your local Lineage Power representative  
for details.  
Module Present Signal: The power supply alerts  
the system when it is properly plugged in via a  
500resistor in series between this signal and  
Logic GRD.  
Protocol Select: This pin must remain a no-  
connect. Do not connect to either output or  
Logic_GRD.  
Hot Plug  
When rapidly extracting and reinserting modules  
care should be taken to allow for discharging the  
internal bias supply so that a predictable restart  
could be achieved. The way to ensure that the  
circuit sufficiently discharges is to observe the  
spinning of the fans after an extraction. The unit  
should not be reinserted until the fans stop  
spinning.  
Enable: On/Off control when I2C communications  
are utilized as configured by the Protocol pin. This  
pin must be pulled low to turn ON the power  
supply. The power supply will turn OFF if either the  
Enable or the ON/OFF pin is released. This signal  
is referenced to Logic_GRD.  
ON/OFF: This is a short pin utilized for hot-plug  
applications to ensure that the power supply turns  
OFF before the power pins are disengaged. It also  
ensures that the power supply turns ON only after  
the power pins have been engaged. Must be  
connected to V_OUT (-DC).  
Without bleeding down internal bias the module  
may remember its last assigned address and may  
not configure itself properly if reinserted into  
another slot.  
Control Definitions  
All signals are referenced to Logic_GRD unless  
otherwise noted. See the Signal Definitions Table  
at the end of this document for further description  
of all the signals.  
Output Signals  
Power_OK: This signal is HI when the main output  
is present and goes LO when the main output is not  
present.  
Input Signals  
I_limit: This signal is HI when the main output is  
not in current limit and goes LO when current limit  
has activated.  
Margining: Set point of the PEM can be changed  
via this input pin. Programming can be either a  
voltage source or a resistance divider. The  
margining pin is connected to 3.3Vdc via a 10kΩ  
resistor inside the PEM. See graphs below.  
Alert #: I2C interrupt signal.  
-58  
3.3Vdc  
Fault: This signal goes LO for any failure that  
requires PEM replacement. Some of these faults  
may be due to:  
Fan failure  
-46  
-44  
Vcontrol  
Over-temperature condition  
Over-temperature shutdown  
Over-voltage shutdown  
Internal PEM Fault  
0
0.1  
An open circuit on this pin reverts the voltage level  
back to the original setting.  
Lineage Power  