155W Single Output with Battery Charger(UPS Function)
Features :
Universal AC input / Full range
AD-155
series
Protections: Short circuit / Overload / Over voltage
Battery low and battery polarity protection
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at PFC 67KHz, PWM 134KHz
2 years warranty
SPECIFICATION
MODEL
OUTPUT NUMBER
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION
OVER VOLTAGE
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS
NOTE
AD-155A
CH1
13.8V
10.5A
0 ~ 11.5A
151.55W
--------
--------
--------
--------
CH1: 12 ~ 14.5V
2.0%
0.5%
0.5%
24ms/230VAC
88 ~ 264VAC
47 ~ 63Hz
PF>0.92 at full load
80%
2.5A/115VAC
1.5A/230VAC
COLD START 20A/115VAC
<1mA / 240VAC
CH2
13.3V
0.5A
0 ~ 0.5A
AD-155B
CH1
27.6V
5A
0 ~ 5.5A
151.55W
150mVp-p
CH1: 24 ~ 29V
1.0%
0.5%
0.5%
2000ms, 90ms/115VAC at full load
--------
--------
--------
--------
CH2
27.1V
0.5A
0 ~ 0.5A
AD-155C
CH1
54V
2.7A
0 ~ 2.7A
156.5W
240mVp-p
CH1: 48 ~ 58V
1.0%
0.5%
0.5%
--------
--------
--------
--------
CH2
53.5V
0.2A
0 ~ 0.5A
RIPPLE & NOISE (max.)
Note.2
150mVp-p
1000ms, 90ms/230VAC
20ms/115VAC at full load
124 ~ 370VDC
84%
40A/230VAC
84%
CH1:105 ~ 135%
CH2:0.51 ~ 0.9A rated output power
Protection type : AC Charging Mode : Constant current limiting, recovers automatically after fault condition is removed
UPS Mode : Protected by internal fuse
CH1:31.74 ~ 37.26V
CH1:62.1 ~ 72.9V
CH1:15.87 ~ 18.63V
Protection type : Shut down o/p voltage, re-power on to recover
19.5V(+1.5V,-1V )
10V 0.8V
-10 ~ +60
-20 ~ +85
(Refer to "Derating Curve")
, 10 ~ 95% RH
20 ~ 90% RH non-condensing
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
183.3K hrs min. MIL-HDBK-217F (25
199*110*50mm (L*W*H)
0.88Kg; 16pcs/15Kg/0.95CUFT
)
39V 2V
DIMENSION
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)