欢迎访问ic37.com |
会员登录 免费注册
发布采购

D-120A 参数 Datasheet PDF下载

D-120A图片预览
型号: D-120A
PDF下载: 下载PDF文件 查看货源
内容描述: 120W双路输出开关电源 [120W Dual Output Switching Power Supply]
分类和应用: 开关
文件页数/大小: 2 页 / 453 K
品牌: MEANWELL [ MEAN WELL ENTERPRISES CO., LTD. ]
 浏览型号D-120A的Datasheet PDF文件第2页  
120W Dual Output Switching Power Supply
Features :
AC input range selected by switch
D-120
series
Protections:Short circuit/Over load/Over voltage
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at 28KHz
2 years warranty
SPECIFICATION
MODEL
OUTPUT NUMBER
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE, HOLD TIME
VOLTAGE RANGE
FREQUENCY RANGE
INPUT
EFFICIENCY (Typ.)
AC CURRENT
INRUSH CURRENT (max.)
LEAKAGE CURRENT
OVER LOAD
PROTECTION
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
D-120A
CH1
5V
12A
2 ~ 12A
120W
120mVp-p
6.0%
1.0%
5.0%
CH1: 4.75 ~ 5.5V
2.0%
0.5%
0.5%
200ms, 50ms, 20ms at full load
88 ~ 132VAC/176 ~ 264VAC selected by switch
47 ~ 63Hz
78%
2.8A/115VAC
1.6A/230VAC
COLD START 35A
<3.5mA / 240VAC
105 ~ 135% rated output power
Protection type : Shut down o/p voltage, re-power on to recover
CH1:5.75 ~ 6.75VDC
Protection type : Shut down o/p voltage, re-power on to recover
-10 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0~50 ) on +5V output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 Approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
80%
248 ~ 370VDC
CH2
12V
5A
0.5 ~ 5A
D-120B
CH1
5V
6A
2 ~ 10A
126W
60mVp-p
2.0%
0.5%
0.5%
150mVp-p
7.0%
1.0%
6.0%
CH2
24V
4A
0.4 ~ 4A
RIPPLE & NOISE (max.)
Note.2
60mVp-p
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
SAFETY & ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
Compliance to EN55022 (CISPR22) Class B
EMC
(Note 4)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A
272.8K hrs min. MIL-HDBK-217F (25 )
199*110*50mm (L*W*H)
0.82Kg; 16pcs/14.2Kg/0.95CUFT
OTHERS
DIMENSION
PACKING
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:D-120-SPEC 2004-11-30