150W U-Bracket Single Output with PFC Function
Features :
ULP-150
series
Universal AC input / Full range(up to 295VAC)
Built in active PFC compliance to EN61000-3-2 class C
Constant Voltage design
High efficiency up to 93%
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Half encapsulated
U-bracket low profile:33mm
ZVS technology to reduce power dissipation
Suitable for built-in type LED applications
3 years warranty
SPECIFICATION
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
ULP-150-12
12V
12.5A
0 ~ 12.5A
ULP-150-15
15V
10A
0 ~ 10A
150W
150mVp-p
13.5~16.5V
2.0%
0.5%
1.0%
ULP-150-24
24V
6.3A
0 ~ 6.3A
151.2W
150mVp-p
21.6~26.4V
2.0%
0.5%
1.0%
ULP-150-36
36V
4.2A
0 ~ 4.2A
151.2W
250mVp-p
32.4~39.6V
2.0%
0.5%
1.0%
ULP-150-48
48V
3.2A
0 ~ 3.2A
153.6W
250mVp-p
43.2~52.8V
2.0%
0.5%
1.0%
OUTPUT
RATED POWER
150W
RIPPLE & NOISE (max.)
Note.2
100mVp-p
VOLTAGE ADJ. RANGE
11.0~13.2V
VOLTAGE TOLERANCE
Note.3
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
2.0%
0.5%
1.0%
2000ms, 100ms/230VAC
16ms/230VAC
Note.4
90 ~ 295VAC
47 ~ 63Hz
PF 0.96/230VAC
3000ms, 100ms/115VAC at full load
16ms/115VAC at full load
127 ~ 417VDC
PF
0.98/115VAC
PF 0.94/277VAC at full load; PF 0.9/230VAC at 50%~100% load
93%
93%
93%
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
91.5%
91.5%
2A/115VAC
1A/230VAC
Cold start 65A/230VAC
<0.75mA / 277VAC
130~185% rated output power
PROTECTION
SHORT CIRCUIT
OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Hiccup mode, recovers automatically after fault condition is removed
17 ~ 21V
26.7 ~ 32.4V
41.4 ~ 48.6V
13.6 ~ 16.3V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
95
5 (RTH2)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-30 ~ +70
(Refer to output load derating curve)
20 ~ 90% RH non-condensing
53 ~ 64.8V
ENVIRONMENT STORAGE TEMP., HUMIDITY
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 60
TEMP. COEFFICIENT
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
VIBRATION
Design refer to EN61347-2-13,IEC61347-2-13,UL8750
SAFETY STANDARDS
WITHSTAND VOLTAGE
Note.6
I/P-O/P:3.75KVAC I/P-FG:1.88KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/25 / 70%RH
EMI CONDUCTION & RADIATION
Compliance to EN55015 Class B
Compliance to EN61000-3-2 Class C( 60% load),EN61000-3-3
HARMONIC CURRENT
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61547, EN55024, light industry level (surge 4KV), criteria A
EMS IMMUNITY
MTBF
OTHERS
DIMENSION
PACKING
216.3K hrs min.
MIL-HDBK-217F (25
)
215*67.4*33mm (L*W*H)
0.67kg; 24PCS/17.5kg/0.65CUFT
SAFETY &
EMC
(Note 5)
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltages. Please check the static characteristics for more details.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
6. Please remove the component D1 before conducted Hipot test.
File Name:ULP-150-SPEC 2011-02-23