欢迎访问ic37.com |
会员登录 免费注册
发布采购

DRP-240-24 参数 Datasheet PDF下载

DRP-240-24图片预览
型号: DRP-240-24
PDF下载: 下载PDF文件 查看货源
内容描述: 低成本,工业240W , DIN导轨安装AC / DC电源 [Low Cost, Industrial 240W, DIN Rail Mount AC/DC Power Supplies]
分类和应用: 功率因数校正输出元件输入元件
文件页数/大小: 2 页 / 117 K
品牌: MPD [ MICROPOWER DIRECT, LLC ]
 浏览型号DRP-240-24的Datasheet PDF文件第1页  
Model Selection Guide
Model
Number
DRP-240-24
DRP-240-48
Rated
Power
(W)
240
240
Input
Voltage
(VAC)
Range
85 - 264
85 - 264
Current (A)
115 VAC
2.8
2.8
230 VAC
1.4
1.4
Voltage
(VDC)
24
48
Output
Current (A)
Max)
10
5
Current (A)
Range
0 ~ 10
0~5
Efficiency
(%, Typ)
84
85
Fuse Rating
Slow-Blow
(A)
6.3
6.3
Notes:
1. Output voltage tolerance includes set-up tolerance, line regulation and
load regulation.
2. Ripple & noise is measured using equipment with 20 Mhz of bandwidth.
Connection to the unit under test is made with a 12 inch length of “twisted
pair” wires terminated with a set of 1.0
μF
& 4.7
μF
capacitors connected
in parallel.
3. Overload protection is foldback current limiting. The unit recovers auto-
matically when the fault is removed.
4. Over voltage protection is a clamp type. The power to the unit must be
manually reset to recover.
5. Over temperature protection shuts down the output. The unit recovers
automatically when the temperature goes down. The thermal detector
is mounted on the heat sink of the power semiconductor.
6. Isolation resistance is given for Input/Output; Input/FG and Output/FG.
7. To mount the unit to the DIN rail, tilt the unit rearwards from the top,
fitting the mount over the top of the rail. Press back on the bottom front
of the unit until it locks in place on the rail. To remove the unit from the
rail, pull the removal clip at the bottom rear of the unit downward with
a screw driver. With the clip down, lift up on the unit from the bottom
front until it clears the rail. Before installation or removal all wiring should
be disconnected and the main power to the system shut off.
8. When wiring the supply, all lines should be as thick and short as possible.
AWG 14 wire is recommended for the
DRP-240
series.
9. The units should be mounted so they are vertically orientated. Air flow
(if it is provided) would optimally flow from the bottom to the top of
the unit.
10. It is recommended that a fuse be used on the input of a power supply
for protection. See the table above for the correct rating.
Derating Curve -
Output Power vs Ambient Temperature
Derating Curve -
Output Power vs Input Voltage
Mechanical Dimensions
Terminal Connections -
TB1
Pin
1
2
3
Function
Frame Ground (FG)
AC/Neutral
AC/Live
Terminal Connections -
TB2
Pin
1,2
3,4
Function
DC Output (+V)
DC Output (-V)
Mechanical Notes:
All dimensions are typical in inches (mm)
Tolerance x.xx = ±0.01 (±0.25)
MicroPower Direct
www.micropowerdirect.com
232 Tosca Drive Stoughton, MA 02072
TEL: (781) 344-8226
FAX: (781) 344-8481
E-Mail: sales@micropowerdirect.com