A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
1750-XC6DT2
1750 ekW
/
60 Hz
/
Standby
1600 ekW
/
60 Hz
/
Prime
480 - 4160V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V**
3
0.8
60
1750
2187.5
2631
4700
743RSL4052
130°C/27°C
4 BAR WYE
600V**
3
0.8
60
1750
2187.5
2105
3600
744RSS4292
125°C/40°C
4 LEAD WYE
4160V
3
0.8
60
1750
2187.5
304
4000
743FSM4370
130°C/27°C
6 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
480V
3
0.8
60
1600
2000
2406
4700
743RSL4052
105°C/40°C
4 BAR WYE
600V
3
0.8
60
1600
2000
1925
3600
744RSS4292
105°C/40°C
4 LEAD WYE
4160V
3
0.8
60
1600
2000
278
4000
743FSM4370
105°C/40°C
6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered