A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
35-JC6DT3
35 ekW
/
60 Hz
/
Standby
30 ekW
/
60 Hz
/
Prime
208 - 600V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
35
35
146
52
361CSL1600
130°C/27°C
12 LEAD ZIG-ZAG
240V**
1
1.0
60
35
35
146
99
284CSL1550
130°C/27°C
4 LEAD
208V**
3
0.8
60
35
43.75
121
92
284CSL1508
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
35
43.75
105
122
284CSL1508
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
35
43.75
53
122
284CSL1508
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
35
43.75
42
123
284PSL1752
125°C/40°C
4 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V
1
1.0
60
30
30
125
66
361CSL1600
105°C/40°C
12 LEAD ZIG-ZAG
240V
1
1.0
60
30
30
125
102
284CSL1550
105°C/40°C
4 LEAD
208V
3
0.8
60
30
37.5
104
93
284CSL1508
105°C/40°C
12 LEAD LOW WYE
240V
3
0.8
60
30
37.5
90
93
284CSL1508
105°C/40°C
12 LEAD HI DELTA
480V
3
0.8
60
30
37.5
45
123
284CSL1508
105°C/40°C
12 LEAD HI WYE
600V
3
0.8
60
30
37.5
36
123
284PSL1752
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered