A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
450-XC6DT3
450 ekW
/
60 Hz
/
Standby
415 ekW
/
60 Hz
/
Prime
208 - 4160V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
450
450
1875
770
574RSL4037
130°C/27°C
12 LEAD ZIG-ZAG
208V**
3
0.8
60
450
562.5
1561
1300
572RSL4027
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
450
562.5
1353
1320
572RSL4027
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
450
562.5
677
1100
572RSL4025
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
450
562.5
541
1040
572RSS4270
125°C/40°C
4 LEAD WYE
4160V
3
0.8
60
450
562.5
78
1240
573FSM4354
130°C/27°C
6 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V
1
1.0
60
415
415
1729
770
574RSL4037
105°C/40°C
12 LEAD ZIG-ZAG
208V
3
0.8
60
415
518.75
1440
1300
572RSL4027
105°C/40°C
12 LEAD LOW WYE
240V
3
0.8
60
415
518.75
1248
1320
572RSL4027
105°C/40°C
12 LEAD HI DELTA
480V
3
0.8
60
415
518.75
624
1100
572RSL4025
105°C/40°C
12 LEAD HI WYE
600V
3
0.8
60
415
518.75
499
1040
572RSS4270
105°C/40°C
4 LEAD WYE
4160V
3
0.8
60
415
518.75
72
1240
573FSM4354
105°C/40°C
6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered