A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
500-VC6DT2
500 ekW
/
60 Hz
/
Standby
455 ekW
/
60 Hz
/
Prime
208 - 600V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
500
625
1735
1430
572RSL4031
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
500
625
1504
1430
572RSL4031
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
500
625
752
1475
572RSL4029
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
500
625
601
1430
572RSL4272
125°C/40°C
4 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
455
568.75
1579
1430
572RSL4031
105°C/40°C
12 LEAD LOW WYE
240V**
3
0.8
60
455
568.75
1368
1430
572RSL4031
105°C/40°C
12 LEAD HI DELTA
480V**
3
0.8
60
455
568.75
684
1475
572RSL4029
105°C/40°C
12 LEAD HI WYE
600V**
3
0.8
60
455
568.75
547
1430
572RSL4272
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered