A tognum grouP BrAnd
DIESEL ENGINE-GENERATOR SET
600-VC6DT2
600 ekW
/
60 Hz
/
Standby
550 ekW
/
60 Hz
/
Prime
208 - 4160V
SySTEm RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
600
750
2082
1750
573RSL4033
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
600
750
1804
1750
573RSL4033
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
600
750
902
1450
572RSL4031
130°C/27°C
12 LEAD HI WYE
600V**
3
0.8
60
600
750
722
1450
572RSS4272
125°C/40°C
4 LEAD WYE
4160V
3
0.8
60
600
750
104
1550
574FSM4356
130°C/27°C
6 LEAD WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V
3
0.8
60
550
687.5
1908
1750
573RSL4033
105°C/40°C
12 LEAD LOW WYE
240V
3
0.8
60
550
687.5
1654
1750
573RSL4033
105°C/40°C
12 LEAD HI DELTA
480V
3
0.8
60
550
687.5
827
1450
572RSL4031
105°C/40°C
12 LEAD HI WYE
600V
3
0.8
60
550
687.5
662
1450
572RSS4272
105°C/40°C
4 LEAD WYE
4160V
3
0.8
60
550
687.5
95
1550
573FSM4356
105°C/40°C
6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered